beautypg.com

Page 28 maintenance – Toshiba HV6AS User Manual

Page 32

background image

Page 28

MAINTENANCE

Table 2. Check Points for Inspection (cont’d)

Check Point

Check Item

Check Method

Criteria

What to do

Auxiliary
Switch

Terminals loose
or disconnected

Visual
inspection.
Tighten using a
screwdriver.

Make sure terminals are
not loose or disconnected.

Repair if
disconnected.
Tighten if loose.
See Table 1 for
tightening torques.

Case/contacts

Visual
inspection.

Make sure there is no
damage or warping.

Replace if damaged
or warped.

Control
Circuits

Smooth
movement of
motor charging
mechanism

Energize the
control circuit.

Breaker (motor-operated
type) should charge
quickly and smoothly.

If the circuit fails to
operate, check the
cause and repair.

Terminals loose
or disconnected

Visual
inspection.
Tighten using a
screwdriver.

Make sure terminals are
not loose or disconnected.

Repair if
disconnected.
Tighten if loose.
See Table 1 for
tightening torques.

Insulation
Resistance
Measure-
ment

Meaure main
circuit to ground

Megger test at
1000V.

Resistance should be
500M

Ω or greater.

Meaure
between main
circuit terminals

Megger test at
1000V.

Resistance should be
100M

Ω or greater.

Meaure control
circuits to
ground

Megger test at
500V.

Resistance should be
2M

Ω or greater.

If the insulation
resistance is low,
wipe off the vacuum
interrupter and other
insulation surfaces
with a clean dry
cloth and then
repeat the test.