INSTALLATION
Page 11
Do not install this
equipment in areas where
unusual service conditions
exist. Using this equipment
in other than usual service
conditions can result in
equipment failure.
Toshiba HV6AS circuit breakers are intended for
use in usual service conditions as defined in
IEEE C37.20.2. The temperature of the cooling
air (ambient air temperature) surrounding the
breaker should be between the limits of -5
°C
(23
°F) and +40°C (104°F). The altitude of the
equipment installation should not exceed 3300 ft
(1000 m).
In particular, avoid the following installation
conditions:
- Excessive dust
- Corrosive gases
- Extreme variations in temperature
- Very high or low humidity
- Vibrations
- Inclined locations
If there is a chance that condensation can occur
Fig. 8 Typical Circuit Breaker Nameplate
at the installation location, a space heater should
be installed inside the circuit breaker enclosure.
NOTE:
Temperature, altitude or other
conditions outside of the usual limits
may require derating or other special
equipment. Contact your nearest
Toshiba representative for additional
information.
RATING VERIFICATION
Prior to Installation, the maximum fault current
capacity of the power system at the point of
installation should be verified. This value must
not exceed the symmetrical interrupting
capability of the circuit breaker. Fig. 8
illustrates a typical circuit breaker nameplate.
Do not exceed the ratings
specified on the circuit
breaker nameplate or
system accessories.
Underrated equipment can
fail during operation
causing fire, explosion,
severe injury, death, and
property damage.
WARNING
DANGER
HOUSTON, TEXAS U.S.A.
RATED VOLTAGE
FREQUENCY
IMPULSE LEVEL
DIELECTRIC
SER. No.
PARTS & WIRING, SEE INSTRUCTIONS
CONTINUOUS AMPS
WEIGHT
SHORT CKT. AMPS
INTERRUPTING TIME
VACUUM CIRCUIT BREAKER
UV TRIP VOLTS
MFG. STANDARD
SHUNT TRIP VOLTS
TOSHIBA INTERNATIONAL CORPORATION
CLOSE VOLTS
50/60 Hz
22 kV AC RMS
60 kV, CREST
630A, RMS
kg
MFG. DATE
lbs
HV6AS-
7.2/4.8 kV, RMS
TYPE
JIS C 4603-1990
JEC-2300-1985
120 VAC
VDC
VDC
14/16 kA, RMS
3 CYCLES
24
53
120 VAC / 125
125
GF07Z301
MU-VV
98700221
7/98
TOSHIBA