Tdvdsn series direct vent gas fireplace, Vertical sidewall installation twist lock pipe – Temco Tool 33TDVDSN User Manual
Page 13

13
TDVDSN Series Direct Vent Gas Fireplace
20007890
FP1012
Top vent max run
1/25/00 djt
20' (6m)
7.5' (2.3m
)
Pipe Straps
Every 3’ (914mm)
Firestop/Zero
Clearance Sleeve
Pipe
Straps Every
3’ (914mm)
FP1012
Fig. 11 Support straps for horizontal runs.
•
If a 90° elbow is used in the horizontal vent run 
(level height maintained) the maximum horizontal 
vent length is reduced by 36” (914 mm). This does 
not apply if the 90° elbows are used to increase or 
redirect a vertical rise.
Example: According to the chart the maximum
horizontal vent length in a system with a 7.5’ (2.3 m) 
vertical rise is 20’ (6 m) and if a 90° is required in 
the horizontal vent it must be reduced to 17’ (5.2 m).
In Figure 16, Dimension A plus B must not be
greater than 17’ (5.2 m).
Horizontal plane means no vertical rise exists on this 
portion of the vent assembly. 
•
The maximum number of 90° elbows per side wall 
installations is three (3).
•
If a 90° elbow is fitted directly onto the fireplace 
flange the maximum horizontal vent run before the 
termination or a vertical rise is 36” (914 mm).
3'
(914mm)
FP1237
horizontal plane
12/02
FP1237
Fig. 12 Maximum horizontal vent run.
7.5'
(2.3m)
A
B
A + B = 17' (5.2m) Max.
1 x 90° elbow in horizontal plane = 3’ (914mm)
FP1238
Fig. 13 Maximum vent run with elbows.
•
The maximum number of 45° elbows permitted per 
side wall installation is two (2). These elbows can be 
installed in either the vertical or horizontal run.
•
For each 45° elbow installed in the horizontal run, 
the length of the horizontal run MUST be reduced by 
18” (457 mm). This does not apply if the 45° elbows 
are installed on the vertical part of the vent system.
•
The maximum number of elbow degrees in a system 
is 270°. (Fig. 14)
1
2
3
4
Example: 
 
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total angular variation = 270°
1 + 2 + 3 + 4 = 270°
FP1239
Fig. 14 Maximum number of elbow degrees.
STEP 1
Locate vent opening on the wall. It may be necessary 
to first position the fireplace and measure to obtain hole 
location. Depending on whether the wall is combustible 
or noncombustible, cut opening to size. (Fig. 15) For 
combustible walls first frame in opening.
NOTE: When using flex vent, the opening will have to 
be measured according to the 1” (25 mm) rise in 24” 
(610 mm) vent run. (Minimum 1” (25 mm) rise.)
Combustible Walls: (Fig. 15) Cut a 9³⁄₈”H x 9³⁄₈”W (240 
x 240 mm) hole through the exterior wall and frame as 
shown.
Vertical Sidewall Installation
Twist Lock Pipe