Operator interface – Trane CVHE-SVU01E-ENX39640712050 User Manual
Page 42

CVHE-SVU01E-EN
42
Operator
Interface
Chiller
Description
Units
notes
1. Front Panel Control Type
(Chilled Water, Hot Water), Chilled Water default
2. Front Panel Chilled Water Setpoint
Temperature
1
3. Front Panel Hot Water Setpoint
Temperature
1
4. Front Panel Current Limit Setpoint
Percent
2
5. Front Panel Base Load Command
On or Auto
6. Front Panel Base Load Setpoint
Percent
7. Front Panel Free Cool Command
On or Auto
8. Front Panel Ice Building Command
On or Auto
9. Front Panel Ice Termination Setpoint
Temperature
10. Ice to Normal Cooling Timer
(0-10), 5 Minutes default
11. Differential to Start
Temperature
12. Differential to Stop
Temperature
13. Setpoint Source
*(BAS/EXT/FP, EXT/FP, FP), none default
*Follows hierarchy of selection from left to right (except ice build which is “OR” logic).
Mode Overrides
Description
Units
Default
Monitor Value
Notes
1. Compressor Control Signal
(Auto, Manual [0-100] ),
Auto
Percent Vane Position
Evaporator Leaving Water
7
Temperature, AFD Frequency, if installed
2. Evaporator Water Pump
(Auto, On),
Auto
1) Evaporator Flow status
2) Override Time Remaining
3
3. Condenser Water Pump
(Auto, On),
Auto
1) Condenser Flow status
2) Override Time Remaining
3
4. Oil Pump
(Auto, On),
Auto
1) Differential pressure
2) Override Time Remaining
3
5. Purge Exhaust Circuit Test
(Off, On),
Off
6. Purge Regeneration Cycle
(Off, On),
Off
Carbon Temperature
Feature Settings
Description
Units
1. Chilled Water Reset
(Constant, Outdoor, Return, Disable), Disable
2. Return Reset Ratio
Percent
3. Return Start Reset
Temperature
4. Return Maximum Reset
Temperature
5. Outdoor Reset Ratio
Percent
6. Outdoor Start Reset
Temperature
7. Outdoor Maximum Reset
Temperature
8. External Chilled Water Setpoint
(Enable, Disable), Disable
9. External Current Limit Setpoint
(Enable, Disable), Disable
10. Ice Building Feature Enable
(Enable, Disable), Disable
11. External Base Loading Setpoint
(Enable, Disable), Disable