Operator interface – Trane CVHE-SVU01E-ENX39640712050 User Manual
Page 32

CVHE-SVU01E-EN
32
Operator
Interface
Reference
Top Level Mode
Sub Level Mode
BAS Code
SYSTEM RESET
Boot & Application software part number, self-test, and
configuration validity screens will be present.
NA
Stopped
Local Stop
00
Stopped
Panic Stop
00
Stopped
Diagnostic Shutdown – Manual Reset
00
Run Inhibit
Ice Building Is Complete
100
Run Inhibit
Tracer Inhibit
100
Run Inhibit
External Source Inhibit
100
Run Inhibit
Diagnostic Shutdown – Auto Reset
100
Auto
Waiting For Evaporator Water Flow
58
Auto
Waiting For A Need To Cool
58
Auto
Waiting For A Need To Heat
58
Auto
Power Up Delay Inhibit: MIN:SEC
58
Waiting To Start
Waiting For Condenser Water Flow
70
Waiting To Start
Establishing Oil Pressure
70
Waiting To Start
Pre-Lubrication Time: MIN:SEC
70
Figure 19