FC-21 Flow Computer

SETUP RELAYS

Rly1

Rly2 Rly3 Rly4

RELAY 1 USAGE
RATE TOTAL NA

RELAY 1 DELAY sec
0

RELAY 1 MODE
LO_ALARM HI_ALARM

RELAY 1 DURATION

#####

RELAY 1 SETPOINT

####### gal

RELAY 1 HYSTERESIS

##### gal/m

Advance To

SETUP RELAYS 3, 4

Sub-menus

Display

Notes

6.4.14
SETUP
ANALOG OUTPUT

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

SETUP ANALOG OUTPUT

ANALOG OUTPUT USAGE
Rate Total Temp Dens

ANALOG OUT FLOW TYPE
Vol CVol/Mass

ANALOG OUTPUT RANGE
4-20mA 0-20mA

LS ANALOG OUTPUT

####### gal/m

FS ANALOG OUT 20mA

####### gal/m

ANALOG OUT DAMPING
0.0

Advance To

SETUP RELAYS

Press ENTER when Analog is flashing to
setup the Analog Output.

Select the desired Analog Output Usage.

Only if Rate selected & Flow EQ. = Mass, Cor/Vol
Select the desired Analog Output Flow.

Select the desired current range for the Analog
Output.

Enter desired Analog Output Low Scale Value.
NOTE: Units label will correspond with output

usage type selected.

Enter desired Analog Output Full Scale Value.

Enter the desired Analog Output Damping
Constant.

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

6.4.15
SETUP RELAYS
(Relay 1 & Relay 2)

ENTER

Select the desired Relay for setup.
(Relays 3 & 4 Optional)

If Relay 1 or Relay 2 Selected,
Select Rate, Total or NA.

If Rate selected, enter desired relay activation
delay value.

Select the desired Relay Activation.
Low: Relay activates when reading is below

setpoint.

High:Relay activates when reading is above

setpoint.

If Total Selected, Enter desired Relay
Duration.

Enter the desired Setpoint. The Setpoint can
be edited in run mode using the PRE 1 key
(PRE 2 key for Relay 2).

If Rate, selected, Enter desired Relay
Hysteresis.

NOTE:

In Batch mode,
Relay 1 is reserved
for Preset,
Relay 2 is reserved
for Prewarn.

ENTER