FC-21 Flow Computer

3. Applications

3.1 Liquid Volume

Measurements:
A flowmeter measures the actual volume in a liquid line. A temperature
sensor can also be installed to correct for liquid thermal expansion (see
3.2 Corrected Volume).

Calculations:
• For Flowmeters with Pulse Outputs, Volume flow is calculated using

the flowmeter frequency output and the user entered K-Factor.

• For Flowmeters with Analog Transmitters, Volume flow is calculated

using the measured flowmeter signal and the user entered scale settings.

Output Results:
• Display Results

Flow Rate, Resettable Total, Non-Resettable Total

• Analog Output

Rate or Total

• Pulse Output

Total

• Relay Outputs

Rate or Total Alarms

Applications:
The Flow Computer can monitor actual volume flow and total of any
liquid. Flow alarms are provided via relays and datalogging is available
via analog (4-20mA) and serial outputs.

Liquid Volume

Pulse Input; Average K-Factor

input frequency * time scale factor

Volume Flow =

K-Factor

Analog Input; Linear

Volume Flow = % input * Full Scale Flow

Liquid Volume
Illustration

Calculations