Omega Engineering PSW1000 User Manual
Page 5
CDLY
0,0s...9,9s
Time setting to delete the maximum value memory after
switching point SP1 is reached (manual deletion is still possible)
MIN
-1 ... xxxx
Display of peak value “Min”
CLRL
-----
Delete the minimum value memory
----- no
deletion
clr delete
value
OFFS
-9,9 ...+xx
Measured value offset in bar
CUT
0,0 ... +xx
Cut-off. e.g. signal suppression at measuring range start in bar
DLDS
0,0 ... 9,9s
Time delay for currently displayed value in seconds
ERRC
-----
Error messages:
0: -ok-
no
error
1:
max
exceeding pos. measuring range
2:
min
exceeding neg. measuring range
3:
dig1
switching output 1 error
4:
dig2 switching output 2 error
5:
anao analog output error
6:
sens
sensor error
7:
data
data error (EEProm)
8:
prog program error
9:
cal
calibration error
V7.X
Lev0...Lev2
Programming lock:
Version display with actual input level:
0 :
only display of operating parameters, no changes possible
1 :
only switching points can be set (“max“ and “min“
memories)
2 :
release user level (all operating parameters for customer)
LITH
20 ... 100
Change display brightness 20...100%
(only for units with Dot-Matrix display)
AOZS
(only V7.X)
0 ... 9999
Scale the analog output - start value (e. g. 0 bar = 4 mA)
AOFS
0 ... 9999
Scale the analog output - end value (e. g. 400 bar = 20 mA)
(output signal start value always corresponds to the display ini-
tial value, e. g. 0 bar = 4mA)
Maximum turn-down 4 : 1, i.e. at values below 25 % of the mea-
suring range the analog output is switched off
STNO
-----
Enter the station number at Profibus DP
RECL
-----
SHRT short profile 8 byte
LONG long profile 32 byte
CODE
000...999
Enter the code level: Changes:
Lev1: 471
(up + down five seconds) Lev1-Lev0
Lev2: 740
(up + down + M five seconds) Lev2-Lev0
Lev0: 999
OPT
(onlyV7.X)
-----
Display of the unit options
selection of the Profibus-protocol
5