Os35, Error messages – Omega OS35 User Manual
Page 4
OS35
Infrared Temperature Sensor
Installation Instructions
1. Install OS35 as close as practical to view target material to be measured
2. Wire OS35 with Red to Positive Power, Black to Ground, White to Positive
Output Signal, and Green to Reference Output Signal
3. Measure actual temperature of target material with OS950 Thermometer or
any reliable reference
4. Adjust “offset”, “zero”, or “low cal” on input device to match reading to ac-
tual thermometer reading
5. Installation calibration complete
*Six counts off one count on
**Six counts on one count off
ERROR MESSAGES
Condition
Priority
LED Display
0-5V
0-10V
4-20mA
RS-232
Low Power
1
OFF
Under 0.1V
Under 0.1V
Under 4mA
Not Implemented
Hardware Internal
Errors
2, 13
Uniform Flash
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
Vsig-Offset High
3
Uniform Flash
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
Vsig-Offset Low
4
Uniform Flash
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
EMI
5
Uniform Flash
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
Range Error
6
Uniform Flash
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
High Ambient
7
Long Flash**
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
Low Ambient
8
Short Flash*
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
Too Much Heat
Flow
9
Long Flash**
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
Too Little Heat
Flow
10
Short Flash*
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
High Target
11
Long Flash**
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented
Low Target
12
Short Flash*
Over 4.9V
Over 9.8V
Over 19.7mA
Not Implemented