Klinkmann Automation Omron Ethernet DAServer
37
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3 17014m13
C200HX/C200HG/C200HE PLCs
The following table lists the supported item names for the C200HX, C200HG and
C200HE PLCs.
Memory Area
Prefix
Tag
Type
Address Range
Value
Range
Suffix
Internal Relay Area 1, 2
Special Relay Area 1, 2
(Bit status)
IR
Discrete IR0:00...IR511:15
or
0.00...511.15
0, 1
Internal Relay Area 1, 2
Special Relay Area 1, 2
(Word contents)
IR
Integer
IR0... IR511
or
0…511
(*)
u s b f g l
m d e c
Link Relay Area
(Bit status)
LR
Discrete
LR0:00...LR63:15
0, 1
Link Relay Area
(Word contents)
LR
Integer
LR0... LR63
(*)
Holding Relay Area
(Bit status)
HR
Discrete HR0:00... HR99:15
0, 1
Holding Relay Area
(Word contents)
HR
Integer
HR0... HR99
(*)
u s b f g l
m d e c
Auxiliary Relay Area
(Bit status)
AR
Discrete AR0:00... AR27:15
0, 1
Auxiliary Relay Area
(Word contents)
AR
Integer
AR0... AR27
(*)
u s b f g l
m d e c
Timer/Counter Area
Completion Flag(****)
TC
Discrete
TC0... TC511
0, 1
Timer/Counter Area
(PV)
PV
Integer
PV0... PV511
(*)
u s b f g l
m d e c
Data Memory Area
(Bit status)(**)
DM
Discrete
DM0:00...
DM9999:15
0, 1
Data Memory Area
(Word contents)(**)
DM
Integer
DM0...
DM9999
(*)
u s b f g l
m d e c
Extended Data Memory
Area (Bit status)(***)
EM
Discrete
EM0:00...
EM6143:15
0, 1
Extended Data Memory
Area Word contents(***)
EM
Integer
EM0... EM6143
(*)
u s b f g l
m d e c
Item/point names, corresponding to Internal Relay/Special Relay Area may be without
prefix.
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default
value range for Integer Tag Type is unsigned integer.
(**) Memory area range DM7000…DM9999 is supported only if Expansion DM Area is
allocated on the PLC.
(***) Current bank only (Memory Area code 98).