1 general installation, Clearances to combustibles, 1 canada and the u.s.a – Osburn Stoves by SB I 2200 User Manual
Page 4
3
Section 1.0 - Installation
When installed and operated as described in these instructions, the Osburn Model 2200 Bay Wood Stove is
suitable for use as a freestanding wood stove in either residential or mobile home installations.
The Model 2200 is not intended for installation in a bedroom.
In Canada the CSA B365 Installation Code for Solid Fuel Burning Appliances and Equipment and the CSA
C22.1 Canadian National Electrical Code are to be followed in the absence of local code requirements. In
the USA the ANSI NFPA 70 National Electrical Code and NFPA 211 Standard for Chimneys, Fireplaces,
Vents and Solid Fuel-Burning Appliances are to be followed in the absence of local code requirements.
In addition to the national installation codes, local building and/or fire officials (or other authorities having
jurisdiction) should be contacted to determine what restrictions and installation requirements might locally
apply.
1.1 General
Installation
1. Proper ventilation is required.
2. Do not connect this unit to any air distribution duct.
3. Connect the stove only to a lined masonry chimney conforming to national and local building
codes for use with solid fuel, or to a listed factory built chimney suitable for use with solid fuel.
Clearances To Combustibles
1.2.1 Canada and the U.S.A.
Clearances to any combustibles when measured directly out from the front and up from the top of
The stove must be a minimum of 48" (1219 mm). The stove must also be placed so as to maintain
the minimum clearances to combustible walls specified for the connector used. (See Table 1.1 and
Figure 1.1).
Canada & USA using
Single Walled Connector
Canada & USA using
Horizontal Single Walled
Connector
Canada & USA Mobile
Home & reduced clearance
installations using listed
Double Walled Connector
To Unit:
Sidewall
A
17" (432 mm)
19" (483 mm)
20.5" (521 mm)
Back wall
B
13.5" (343 mm)
13.5" (343 mm)
6.0" (152 mm)
Corner
C
10" (254 mm)
10" (254 mm)
3.0" (76 mm)
To Connector:
Sidewall D
27" (686 mm)
29" (737 mm)
30" (762 mm)
Backwall E
16" (406 mm)
16" (406 mm)
7.25" (184 mm)
Corner F
20" (508 mm)
20" (508 mm)
13" (330 mm)
Table 1.1
Minimum
Clearances to Combustible Materials – Canada and the U.S.A.