Section 16: removal and replacement parts, 1 gas valve, 35, step 16.1 – Roberts Gorden COMBAT CTU 22 TO 115 User Manual
Page 41

SECTION 16: R
EMOVAL
AND
R
EPLACEMENT
P
ARTS
35
SECTION 16: REMOVAL AND REPLACEMENT PARTS
See warnings and notes
before removing or replacing parts.
Burner Components
All serviceable burner parts are accessed by the
door on the right side of the heater. Use a
screwdriver to turn the latch 90°.
16.1 Gas Valve
Remove the gas supply pipe at the heater inlet.
16.1.1
Disconnect
wire harness
Unplug
control
from
valve
Remove
fixing
screw
Ignition
Control
Description
Part Number
Gas Valve VR4105A
90033403
Ignition Control
90434010
Models 22 - 60
16.1.2
Step 1
Unscrew
gas pipe
from the
valve inlet.
Step 2
Unscrew valve from the
burner manifold
or
unscrew the fixing screws for
the inlet and outlet flanges.
Unplug
electrical lead.
(rectifier harness)
Ignition
Control
Description
Part Number
Gas Valve VR4605
90033404
Ignition Control
90434020
Models 75 - 115
16.1.3 All Models
Replace in reverse order. Verify that the gas flow
direction of the valve is correct. Use a minimum
amount of gas seal on the thread joint. Re-use the
"O" ring seal in the outlet flange where fitted. Check
that all the joints are leak free. Reset gas valve.
IT IS IMPORTANT THAT ONLY THE CORRECT
GAS VALVES SPECIFIED FOR EACH MODEL
TYPE ARE USED WHEN REPLACING THESE
CONTROLS.