beautypg.com

Raytherm - type h, Hydronic heating boilers - indoor – Raypak 181-401 User Manual

Page 2

background image

Catalog No.: 2000.203E

Effective: 12-1-07

Replaces: 4-1-05

Raytherm - Type H

Hydronic Heating Boilers - Indoor

Model



Dimensions (Inches)

Shipping Weight

(Lbs.) – Approx.

Model

No.

MBTU

Input

MBTU

Output

AFUE

(%)

Width

A

Height

C

J

Flue Dia.

K

No Pump w/ Pump

H-181* 181 148 82.6 18-1/4 62-5/8 12-1/16

6

191

221

H-261 264 216 82.7 22-3/8

62-7/8 11-1/8

7

214

244

H-331

334 274 N/A

25-3/4

63-3/4 10-3/4

8

234

264

H-401*

399 327 N/A

29-1/4 65-3/8 12-1/2

9

253

283

* Exceptions on H3 (two-stage-fired) models:

- Model H3-181 has an 18-1/4” gas connection
- Model H3-401 has 375 MBTU Input and 308 MBTU Output

NOTE: Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000, reduce ratings at the rate of 4% for each

1,000 feet above sea level.

BOILER RATE OF FLOW AND PRESSURE DROP

10°

T

20°

T

30°

T

Model

No.

GPM

P FT

GPM

P FT

GPM

P FT

H-181 30 4.2 N/A N/A N/A N/A
H-261 43 8.5 22 2.2 N/A N/A
H-331 N/A N/A 27 3.4 N/A N/A

H-401

N/A N/A 33 5.2 22 2.3

N/A – Not Applicable

Low NOx

*

Raypak, Inc.

ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com