beautypg.com

Raytherm - type wh, A/2 l, Model – Raypak Raytherm - Type WH 962-1826 User Manual

Page 2

background image

Catalog No.: 3500.23D

Effective: 1-15-08

Replaces: 7-15-04

Raytherm - Type WH

Models 962-1826

Model


11 3/4

14 1/2

5

A/2

L

1 1/8

COMBUSTIBLE FLOOR SHIELD

14

5 1/8

2 1/2

G

GAS

ELEC.

CONN.

27 3/4

C

J

B

11 1/4

6

32 1/2

19 1/2

(J-BOX)

PUMP

(OPTIONAL)

H

IN

OUT

K

INDOOR

DRAFT

HOOD

11 1/8

(OPTIONAL)

MODELS 962 THRU 1826

Dimensions

(Inches)

Model MBTUH

Overall

Jacket

Gas

Water

Flue

Shipping

Weight

No. Natural

Gas

Width

Height

Height

Conn. Conns.

Dia.

Lbs.

(Approx.)

Input

Output

A B C G H J K

L

Less

Pump

w/Pump

WH-962 961.7 788.6

52-3/8

76-1/8

33-1/2

1

2-1/2

23-5/8

14

28 705 760

WH-1125 1124.7 922.0 59-1/4 78-1/8 33-1/2 1 2-1/2

23-5/8

16 32 745

800

WH-1223 1222.5 1002.4 63-5/8 78-1/8 33-1/2 1-1/4 2-1/2 23-5/8 16 32

805

860

WH-1336 1336.6 1096.0 68-5/8 80-1/8 33-1/2 1-1/4 2-1/2 23-5/8 18 36

875

930

WH-1468 1467.0 1203.0 74-7/8 80-1/8 33-1/2 1-1/4 2-1/2 23-5/8 18 36

945

1000

WH-1631 1630.0 1336.6 81-1/8 83-1/8 36-1/2 1-1/4 2-1/2 23-5/8 18 36

985

1040

WH-1826 1825.6 1497.0 89-3/8 85-1/8 36-1/2 1-1/4 2-1/2 23-5/8 20 40

1035

1090

NOTES: Ratings are shown for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for each 1,000 feet above

sea level.

HEATER RECOVERY RATES (GPH)

Temperature Rise

Model

No.

20°F 30°F 40°F 50°F 60°F 80°F 100°F

WH-962

4733

3156

2367 1893 1578 1183

947

WH-1125

5536 3690 2768 2214 1845 1384 1107

WH-1223

6017 4011 3009 2407 2006 11504

1203

WH-1336

6579 4386 3289 2631 2193 1645 1316

WH-1468

7221 4818 3610 2888 2407 1805 1444

WH-1631

8023 5349 4011 3209 2674 2006 1605

WH-1826

8986 5990 4493 3594 2995 2246 1797

HEATER RATES OF FLOW AND PRESSURE DROPS

20°

T 30°

T 40°

T

Model

No.

GPM

P (ft) GPM P (ft) GPM P (ft)

WH-962 79 8.5 53 3.8 N/A N/A
WH-1125

N/A N/A 61 5.5 46 3.1

WH-1223

N/A N/A 67 7.0 50 3.9

WH-1336

N/A N/A 73 8.6 55 4.9

WH-1468

N/A N/A 80 11.0 60 6.2

WH-1631

N/A N/A 90 14.8 67 8.0

WH-1826 N/A N/A N/A N/A 75 10.6

NOTE: Maximum acceptable flow through heat exchanger tubes

is 90GPM.

Raypak, Inc.

ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com