background image

Catalog No.: 3500.24C

Effective: 08-10-11

Replaces: 01-15-08

Raytherm - Type WH

Models 2100-4100

Model

MODELS WH 2100 – 4001

MBTUH Width

Overall

Height

Gas

Conn.

Water
Conn.

Flue

Dia.

Model

No.

Input Output A

B

G

H

K

Approx.

Shipping

Weight (lbs)

WH-2100 2100 1722

61 68-1/4

*

3

24

1400

WH-2500 2499 2049

70 68-1/4

*

3

26

1580

WH-3001 3000 2460 81-1/4 68-1/4

2

3

28

1750

WH-3500 3500 2870 92-1/2 68-1/4

2

3

30

1920

WH-4001 4000 3280 103-3/4 68-1/4

2

3

32

2100

* 1-1/2” or 2”, contingent on water heater type code requirements
NOTES: Dimensions are in inches.

Ratings are for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings
4% for every 1,000 feet above sea level.

HEATER RATES OF FLOW AND PRESSURE DROPS

20°F

ΔT 30°F

ΔT 40°F

ΔT

Model

No.

GPM

ΔP (ft) GPM ΔP (ft) GPM ΔP (ft)

WH-2100 172 11.0 115 4.9 N/A N/A
WH-2500 N/A N/A 137 7.5 102 4.3
WH-3001 N/A N/A 164 11.2 123 6.5
WH-3500 N/A N/A 191 16.8 144 9.3
WH-4001 N/A N/A N/A N/A 164 12.8

Maximum acceptable flow through heat exchanger tubes is
200 GPM.

HEATER RECOVERY RATES (GPH)

Temperature Rise

Model

No.

20°F 30°F 40°F 50°F 60°F 80°F 100°F

WH-2100 10336

6890 5168 4134 3445 2584 2067

WH-2500 12300

8200 6150 4920 4100 3075 2460

WH-3001 14765

9844 7383 5906 4922 3691 2953

WH-3500 17227 11484

8613 6891 5742 4301 3445

WH-4001 19688 13125

9844 7875 6563 4922 3938

Raypak, Inc. ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com

Electrical Rating

Models

W/Pump

W/O

Pump

951276

pump*

11 Amps @

230VAC

2100-

4001

22 Amps @

110VAC

< 8 Amp

@

120VAC

* Pump requires separate