FPI U31-2 Gas Fireplace Insert

INSTALLATION

IMPORTANT:

SAVE THESE

INSTRUCTIONS

The FPI Gas Insert must be installed in ac-
cordance with these instructions. Carefully read
all the instructions in this manual fi rst. Consult
the building authority having jurisdiction to de-
termine the need for a permit prior to starting
the installation.

NOTE: Failure to follow the instructions

could cause a malfunction of the
heater which could result in death,
serious bodily injury, and/or prop-
erty damage. Failure to follow
these instructions may also void
your fi re insurance and/or warranty.
This appliance can be used with a
thermostat.

FOR YOUR SAFETY

This appliance requires air for proper combus-
tion. Always provide adequate combustion
and ventilation air. Follow instructions and
information in CAN/CGA B149 (in Canada) or
the National Fuel Gas Code ANSI Z223.1 (in the
USA), regarding requirements for combustion
and ventilation air.

SPECIFICATIONS

At pressures over 1/2 psig, the pipe to the unit
must be disconnected.

Gas Input Capacity:
Natural

Gas

30,000

Btu/h

Propane

27,500

Btu/h

Min. Output (Fan Off)
Natural

Gas

21,000

Btu/h

Propane

19,400

Btu/h

Max. Output (Fan On)
Natural

Gas

22,000

Btu/h

Propane

20,500

Btu/h

Fuels: Approved for use with both natural
gas, and propane. Approved as is for use at
0' to 2,000'. With a fi eld installed conversion
kit 0' - 4,500'.

Electrical: 120V A.C. system.

Circulation Fan: Variable speed, 127 CFM.

Log Set: Ceramic fi bre, 7 per set.

Vent System: Minimum 4" B-Vent or listed
gas fuel vent liner.

GAS PRESSURE TESTING

The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at test pres-
sures over 1/2 psig (3.45 kPa).

POLICY FOR SOLID

FUEL BURNING AND

FACTORY BUILT

FIREPLACES

The FPI U31-2 may be installed and vented into
any solid fuel fi replace that has been installed
in accordance with the National, Provincial and
local building codes and is constructed of non-
combustible materials.

1) Installer must mechanically attach the sup-

plied label to the inside of the fi rebox of the
fi replace into which the gas fi replace insert
is installed.

WARNING: This fi replace has been con-
verted for use with a gas fi replace insert
only and cannot be used for burning wood
or solid fuels unless all original parts have
been replaced, and the fi replace re-approved
by the authority having jurisdiction.

2) Do not cut any sheet-metal parts of the

fi replace, in which the gas fi replace insert
is to be installed.

3) If the factory-built fi replace has no gas access

hole(s) provided, an access hole of 1-1/2"
(37.5mm) or less may be drilled though
the lower sides or bottom of the fi rebox in
a proper workmanship like manner. This
access hole must be plugged with a non-
combustible insulation after the gas supply
line has been installed.

4) The fi replace fl ue damper can be fully

blocked open or removed for installation of
the gas fi replace insert.

5) The fi replace and fi replace chimney must

be clean and in good working order and
constructed of non-combustible materials.

6) The

chimney

cleanouts

must

t

properly.

7) Refractory (fi rebricks), glass doors, screen

rails, screen mesh and log grates can be
removed from the fi replace before installing
the gas fi replace insert.

8) Smoke shelves, shields and baffl es may be

removed if attached by mechanical fasten-

ers. If any part is removed it must not weaken
the structural integrity of the factory built.

9) Trim panels or surrounds shall not seal

ventilation openings in the fi replace.

BEFORE YOU START

Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:

General Safety Information

1) The appliance installation must conform

with local codes or in the absence of local
codes, with CAN/CGA B149 (in Canada)
or the National Fuel Gas Code ANSI
Z223.1. This appliance should be installed
by a qualifi ed gas fi tter technician only.

2) Installation and repair should be done

by a qualifi ed service person.

3) The appliance should be inspected before

use and at least annually by a professional
service person. More frequent cleaning
may be required due to excessive lint from
carpeting, bedding material, animal hair, etc.
It is imperative that control compartments,
burners and circulating air passageways of
the appliance be kept clean.


4) See general construction and assembly

instructions. This appliance may only be
installed in a vented, noncombustible fi re-
place.

5) This appliance is Listed for bedroom instal-

lations. In Canada room heaters must be
installed with a Listed Millivolt Thermostat.
Some areas may have further requirements,
check local codes before installation.

6) This unit is not approved for installation into

a mobile home.

7) Always connect this insert to a vent sys-

tem venting to the outside of the building
envelope. Never vent to another room or
inside a building. Make sure that the vent
is properly sized and is of adequate height
to provide the proper draft.

8) Inspect the venting system annually for

blockage and any signs of deterioration.


9) Any glass removed for servicing must be

replaced prior to operating the appliance.


10) To prevent injury, do not allow anyone who

is unfamiliar with the operation to use the
fi replace.