beautypg.com

Hi delta – type h, Model – Raypak 302BE-902BE User Manual

Page 2

background image

Catalog No.:

2000.441E

Effective: 11-15-07

Replaces: 1-1-07

Hi Delta – Type H

Models 302BE-902BE, 87% Efficiency

Model

RATES OF FLOW AND PRESSURE DROPS

10°F

T 20°F

T

30°F

T

Min. Flow

Max. Flow

Model GPM

P (ft)

GPM

P (ft)

GPM

P (ft)

GPM

P (ft)

T

GPM

P (ft)

T

302BE 52 3.4 26 <1

N/A

N/A

20

<1

26

90

9.8 6

402BE

69 5.8 35 1.5 23 <1 20 <1 35

90 10.0

8

502BE

87 9.9 44 2.5 29 1.2 22 <1 40

90 10.5

10

652BE

N/A

N/A 57 4.3 38 2.0 28 1.2

40

90 10.7

13

752BE

N/A

N/A

65 5.8 44 2.7 33 1.7

40

90 11.0

15

902BE

N/A N/A 78 9.0 52 4.1 39 2.4

40

90 11.8

17

Basis is 20 GPM or 40°F

∆T for minimum flow, 90 GPM for maximum flow.

NOTE: Pump location
varies based on model
and application

NOTES: 1. Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer.

2. Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 – 13” WC.

SPECIFICATIONS

Approx.

MBTUH

A

G H

K T W

Amp. Shipping

Model

Input Output Width NPT NPT

Draw Wt.

(Lbs)

302BE

300

261

36

3/4 2 5

6 18

6

380

402BE

399 347 43 3/4 2

6

6

18-1/2

6 445

502BE

500 435 50

1-1/4

2

6

6 22 6 545

652BE

650 566

60-1/2 1-1/4

2

8

6

27-1/4

6 590

752BE

750 653

67-1/2 1-1/4

2

8

6

30-3/4

6 675

902BE

900 783 78

1-1/4

2

8

6 36 7 740

Dimensions are in inches.

Raypak, Inc.

ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com