beautypg.com

Hi delta – type h, Model – Raypak Hydronic Heating Boiler 992BE-2342BE User Manual

Page 2

background image

Catalog No.: 2000.451E

Effective: 11-15-07

Replaces: 1-1-07

Hi Delta – Type H

Models 992BE-2342BE, 87% Efficiency

Model















SPECIFICATIONS

Approx.

MBTUH

Firing

A

H

K

T

W

Amp.

Shipping

Model Input Output Stages Width NPT

Draw* Wt.

(Lbs.)

992BE 990

861

3

57-1/8

2-1/2

10 10

16-13/16

<12

900

1262BE 1260 1096

4

68-1/2 2-1/2

12 10

20-9/16

<12 1010

1532BE 1530 1331

4

79-7/8 2-1/2

12 10

24-3/8

<12 1225

1802BE 1800 1566

4

91-1/8 2-1/2

14 10

28-1/8

<12 1350

2002BE 1999 1739

4

102-1/2 2-1/2

14 10

31-15/16

<12 1450

2072BE 2070 1801

4

102-1/2 2-1/2

14 10

31-15/16

<12 1450

2342BE 2340 2036

4

113-7/8 2-1/2

16 10

35-11/16

<12 1520

Dimensions are in inches.

* Without pump

RATES OF FLOW AND PRESSURE DROPS

20°F

T

30°F

T

Min. Flow

Max. Flow

Model GPM

P (ft) GPM P (ft) GPM P (ft) T GPM P (ft) T

992BE

86

6.0

57

2.7

43 1.6 40

132

14.0

13

1262BE

110

10.7 73 4.9 55 2.8 40 132 15.5 17

1532BE

132

16.5

89 7.6 67 4.4 40 132 16.5 20

1802BE

N/A

N/A

104

11.6 78 6.5 40 132 18.0 24

2002BE

N/A

N/A 116

15.1 87 8.7 40 132 19.5 26

2072BE

N/A

N/A

120

16.2 90 9.3 40 132 19.5 27

2342BE

N/A

N/A

N/A

N/A 102 13.0 40 132 21.0 31

Basis is 30 GPM or 40°F

∆T for minimum flow, 132 GPM for maximum flow.

NOTE: Pump location
varies based on model
and application.

NOTES: 1. Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer.

2. Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 – 13” WC.

Raypak, Inc.

ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com