Cold Water Run Troubleshooting Guide

Step 9

Step 8

Step 10

Step 1

Step 2

Step 3

Step 4

Step 5

Step 6

Step 7

Is there a Call For

Heat at the heater?

Is the 220VAC inverter in the

cold run controller powered?

Replace inverter or install jumper

and correct switch settings

Does the cold run inverter output

12VDC from PCS to pin FS?

Replace circuit board

Are the Economaster and

Interlock leads connected to

N.O. contacts of relay K-6?

Does cold run relay K-6

coil receive 24VAC from

MC on circuit board?

Are the Economaster

and Interlock leads

connected correctly to

heater CPW board?

Call our Technical Service Department

1-800-927-2975 Outside California

1-800-627-2975 Inside California

NO

Verify 120VAC from

TB1 on the heater

and correct

YES

Does TB1 of cold run

controller have 120

VAC?

Heater is in standby mode

Correct Wiring

YES

NO

NO

YES

YES

NO

NO

NO

YES

YES

NO

The unit is okay

YES

NO

YES

Correct wiring

Is the injector pump

modulating after 2-1/2

NO

Correct wiring

YES

Is the heater tripping the high

limit?

YES

NO

Verify pump is rotating in proper

direction

Pump must decrease

RPM’s on decreasing 0-

10VDC signal

YES

Correct 3Ø pump wiring

NO

Is 24VAC present at Poolstat

connection on cold run circuit

board?

Check 24VAC output at J17 of

heater circuit board and correct

Is 0-10VDC present at

connection FR of cold run circuit

board?

NO

Replace cold run circuit board

YES

Does cold run circuit board lock-out on

“Sensor out of Range”?

NO

YES

Is sensor resistance correct?

YES

NO

Replace sensor