Ordering information, Maintenance – model lp dry valve actuator – Reliable Sprinkler RELIABLE Single Interlock Preaction System 6103060028 User Manual
Page 16
Model LP Dry Valve Actuator Parts List
P/N 71030010
Refer to Fig. 8
16.
Note:
For metric installations, a 2" NPT x R2, ISO 7/1 x Close Nipple (Reliable P/N 98543401) is sold separately as an
adapter for the single drain outlet of the trims.
Ordering Information
Specify
Valve Model & Size
— 4”(100mm) Model DDX Deluge Valve (P/N 6103040026), 6”(150mm) Model DDX Deluge Valve
(P/N 6103060024), 165mm Model DDX Deluge Valve (P/N 6103060028).
Trim
— The trim set is available in individual parts, in time-saving segmentally assembled kit forms, or fully assembled
to the Model DDX Deluge Valve.
Item
No.
Part No.
Description
Qty.
Required
1
94106936
Lower Housing
1
2
94106935
Upper Housing
1
3
96006905
Seat
1
4
92206311
Diaphragm
1
5
95106911
Facing Plate Assembly
1
6
96906311
Diaphragm Washer
1
7
94906406
Facing Plate Nut
1
8
95406901
Seat O-Ring
1
9
95606305
Bolt
6
10
96406902
Compression Spring
1
Trim Configurations
Trim Part Numbers
4" (100mm) Valve
6" (150mm) Valve
165mm Valve
Fully Assembled to Model DDX Valve
6505040400
6505060400
6505065400
Segmentally Assembled
(Model DDX Valve Sold Separately)
6502071710
Individual Parts
(Model DDX Valve Sold Separately)
6502071700
Maintenance – Model LP Dry Valve Actuator
Refer to Figs. 7 and 8
1. If water constantly flows through the Model LP Dry
Valve Actuator and into the drain, there is a leak in the
seal of the Actuator’s seat.
2. Close the main valve controlling water supply (Fig. 7) to
the Deluge Valve and close off the air/nitrogen supply
to the sprinkler system. Close valve A (Fig. 7).
3. Drop pressure in the system by opening the ¼” angle
valve, valve E (Fig. 7), and remove the Actuator from
the system.
4. Remove all six bolts (#9, Fig. 8) holding the Actuator to-
gether. Clean or replace the facing plate assembly (#5,
Fig. 8) and seat (#3, Fig. 8).
5. Reassemble the Actuator, using a torque of 8 ft-lbs on
the facing plate nut (#7, Fig. 8) and 12 ft-lbs on the six
bolts (#9, Fig. 8). Use a cross-tightening pattern. Rein-
stall the Actuator. Set up the Model DDX Deluge Valve
as per the section of this bulletin entitle “Resetting the
Single Interlock Preaction System.”