Emi and environmental type tests, Ruggedswitch, Rsg2200 – RuggedCom RSG2200 User Manual
Page 5

www.RuggedCom.com
5
RuggedSwitch
®
RSG2200
RuggedSwitch
®
RSG2200
9-Port Managed Gigabit Ethernet Switch, 128-bit Encryption
EMI and Environmental Type Tests
Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40°C, 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
+85°C, 16 Hours
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (non-condensing), 55°C , 6 cycles
IEC 60255-21-1
Vibration
2g @ (10 - 150) Hz
IEC 60255-21-2
Shock
30g @ 11mS
IEC 61850-3 EMI TYPE TESTS
TEST
Description
Test Levels
Severity Levels
IEC 61000-4-2
ESD
Enclosure Contact
+/- 8kV
4
Enclosure Air
+/- 15kV
4
IEC 61000-4-3
Radiated RFI
Enclosure ports
20 V/m
Note 1
IEC 61000-4-4
Burst (Fast Transient)
Signal ports
+/- 4kV @ 2.5kHz
Note 1
D.C. Power ports
+/- 4kV
4
A.C. Power ports
+/- 4kV
4
Earth ground ports
+/- 4kV
4
IEC 61000-4-5
Surge
Signal ports
+/- 4kV line-to-earth, +/- 2kV line-to-line
4
D.C. Power ports
+/- 2kV line-to-earth, +/- 1kV line-to-line
3
A.C. Power ports
+/- 4kV line-to-earth, +/- 2kV line-to-line
4
IEC 61000-4-6
Induced (Conducted) RFI
Signal ports
10V
3
D.C Power ports
10V
3
A.C. Power ports
10V
3
Earth ground ports
10V
3
IEC 61000-4-8
8 Magnetic Field
Enclosure ports
40 A/m continuous, 1000 A/m for 1 s
Note 1
1000 A/m for 1 s
5
IEC 61000-4-29
Voltage Dips & Interrupts
D.C. Power ports
30% for 0.1s, 60% for 0.1s, 100% for 0.05s
N/A
A.C. Power ports
30% for 1 period, 60% for 50 periods
N/A
IEC 61000-4-11
100% for 5 periods, 100% for 50 periods
N/A
IEC 61000-4-12
Damped Oscillatory
Signal ports
2.5kV common, 1kV diff. mode@1MHz
3
D.C. Power ports
2.5kV common, 1kV diff. mode@1MHz
3
A.C. Power ports
2.5kV common, 1kV diff. mode@1MHz
3
IEC 61000-4-16
Mains Frequency Voltage
Signal ports
30V Continuous, 300V for 1s
4
D.C. Power ports
30V Continuous, 300V for 1s
4
IEC 61000-4-17
Ripple on D.C. Power Supply
D.C. Power ports
10%
3
IEC 60255-5
Dielectric Strength
Signal ports
2kVac (Fail-Safe Relay output)
N/A
D.C. Power ports
1.5kV DC
N/A
A.C. Power ports
2kVac
N/A
IEC 60255-5
H.V. Impulse
Signal ports
5kV (Fail-Safe Relay output)
N/A
D.C. Power ports
5kV
N/A
A.C. Power ports
5kV
N/A
IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS
2
Test
Description
Test Levels
IEEE C37.90.3
ESD
Enclosure Contact
+/-2kV, +/-4kV, +/- 8kV
Enclosure Air
+/-4kV, +/-8kV, +/-15kV
IEEE C37.90.2
Radiated RFI
Enclosure ports
35 V/m
IEEE C37.90.1
Fast Transient
Signal ports
+/- 4kV @ 2.5kHz
D.C. Power ports
+/- 4kV
A.C. Power ports
+/- 4kV
Earth ground ports3
+/- 4kV
IEEE C37.90.1
Oscillatory
Signal ports
2.5kV common mode @1MHz
D.C. Power ports
2.5kV common, 1kV diff. mode@1MHz
A.C. Power ports
2.5kV common, 1kV diff. mode@1MHz
IEEE C37.90
H.V. Impulse
Signal ports
5kV (Fail-Safe Relay output)
D.C. Power ports
5kV
A.C. Power ports
5kV
IEEE C37.90
Dielectric Strength
Signal ports
2kVac
D.C. Power ports
1.5kV DC
A.C. Power ports
2kVac
Notes:
1. Ruggedcom specified severity levels