Adb – type h, Model – Raypak 751-1501 User Manual
Page 2

Catalog No.: 2000.36G
Effective: 2-1-08
Replaces: 5-1-05
ADB – Type H
Models 751-1501
Model
MBTUH
B D E F G
H K M P
Ship
Weight
Foot-
Amps*
Model
Input
Output
Height
NPT
NPT
Flue
∅
(Lbs.)
(Ft
2
)
H 751
750
630
64
38
44-1/2
29-3/4
1-1/2
2
8
17-3/4
41
680
5.4
8
H 1001
999
840
72
46
52-1/2
37-3/4
1-1/2
2-1/2
10
21-1/2
49
720
5.4
10
H 1501
1499
1260
82
56
62-1/2
47-3/4
1-1/2
2-1/2
12
20-1/4
59
780
5.4
12
- Dimensions are in inches.
- Ratings shown are for elevations up to 5,000 feet. For installations at elevations
above 5,000 feet, please consult the factory for additional instructions.
- For direct vent applications, please contact the factory about relocating the pump.
* Current draw does NOT include pump.
(Supply breaker must have delayed trip.)
RATES OF FLOW AND PRESSURE DROPS
20°F
∆T 30°F
∆T 40°F
∆T
Maximum Flow
Minimum Flow
Model GPM
∆P (ft.)
GPM
∆P (ft.)
GPM
∆P (ft.)
GPM
∆P (ft.) ∆T (°F)
GPM
∆P (ft.) ∆T (°F)
H
751 63 5.8 42 2.9 32 1.8 110
17.0 11 32 1.8 40
H
1001
84 11.8 56 5.6 42 3.4 110
20.0 15 42 3.4 40
H
1501
126 31.4 84 14.9 63 9.1 126 31.4 20 63 9.1 40
Certified Clearances
Front
24” (for service)
Rear
12” (water side)
Right 1”
Left 1”
Top
0” (see note 1)
Floor
0” (see note 2)
Vent 1”