Catalog No.: 2000.17

Effective: 6-22-09

Replaces: New

XFyre – Type H

Models 300-850

Model




Dimensions (in.)

MBTUH

Model

(H7-)

Input Output

A

Length

F

Mounting

G

NPT

H

NPT

K

Flue Ø

N

C/A Ø

Ship

Weight

(Lbs.)

Foot-

print
(Ft

2

)

Amps*

300 300 282 28-1/4 27-9/16 3/4

1-1/2 4

4

410 6.6 3

500 500 470 37-1/4 36-1/4 1 1-1/2 4

4

505 7.9 4

850 850 799 54-1/4

53-9/16

1-1/4

2

6

6

580 9.5 5

Ratings shown are for elevations up to 2,000 feet. For installations at elevations
above 2,000 feet, please consult the factory for additional instructions.

* Current draw is for heater only.

(Supply breaker must have delayed trip.)

RATES OF FLOW AND PRESSURE DROPS

20ºF ∆T 30ºF

∆T 40ºF

∆T

Min Flow

Max Flow

Model

(H7-)

GPM

∆P

GPM

∆P

GPM

∆P GPM

∆P

∆T GPM ∆P

∆T

300 28 17 19 8 14 5 14 5 40 36 27 17

500 47 16 31 7 24 4 24 4 40 56 24 18

850 80 40 53 17 40 10 40 10 40 80 40 20

* Closed systems only

CLEARANCES

Certified

Minimum

Recomm.

Service

Front 24”

24”

Rear 24”

24”

Right 1”

1”

Left 1”

1”

Top 12” 24”

Floor 0”

--

Vent 1”

--