The selection of the correct ratio depends on the initial
temperature Set Point set on screen 02 and the
desired system water temperature. If the building is
too cold, increase the ratio value. After changing the
ratio, wait several days and evaluate the comfort level
before making another change.

Advanced Programming

feature

Line 2 may be modified by inserting the building
design characteristics into the formula. The Reset
Ratio will be modified to reflect those characteristics.

NOTE: This information works the same in °C (not

shown for clarity).

7

0

S

U

T

A

T

S

M

E

T

S

Y

S

S

Y

S

T

E

M

N

O

R

M

A

L

Screen number

If more than one ERROR, all errors will be displayed in sequence.

ERROR Indications:

System Status:

To show the status of other boilers in the system, push either the "LEFT" or "RIGHT" button. If the controller is
in a fault condition, the boiler number can be displayed automatically.

NOTE: The alarm horn can be silenced by pushing

the mode button.

NO SAFETY SIGNAL

Safety signal (24VAC) not present on J7 connector

NO CFH SIGNAL

Call-for-heat signal (24VAC) not present on J6 connector

WATER TEMP>MAX

System water temp > Maximum allowed temp

ILS>OLS

Inlet water temp > Outlet water temp

SYS IS OPEN

System water sensor or cable/connector is open

SYS IS SHORT

System water sensor or cable/connector is shorted

OLS IS OPEN

Outlet water sensor or cable/connector is open

OLS IS SHORT

Outlet water sensor or cable/connector is shorted

ILS IS OPEN

Inlet water sensor or cable/connector is open

ILS IS SHORT

Inlet water sensor or cable/connector is shorted

OSS IS OPEN

Outdoor air sensor or cable/connector is open

OSS IS SHORT

Outdoor air sensor or cable/connector is shorted

Message

Meaning

Table H: Error Indications