manual Override

Internal switches have been provided on each of the stage modules that can be used to manually override the
microcontroller. See switch SW1 on each stage board, page 15.

Table E: Control Screens (Continued)

SCREEN

DESCRIPTION

FACTORY DEFAULT

Boiler/Stage Off

Delay

15

0 to 600 seconds; sets the time interval between sequential
boiler start-ups. 0 to 600 seconds; sets time interval
between stages turning off.

Default = 10 seconds

Disabled in PID

Standard or PID 16

Selects either Standard or PID operation. If PID is selected
then PID & Interval is programmable using screen 34.

Default = PID

Boiler Inlet/Outlet

Delta(Optional)

17

Displays the boiler inlet and outlet temperature in °F or °C
and the difference (delta) between them. (Requires 4-sensor
installation, option Y-306.)

INLET / OUTLET =

Delta T

Auto Lead-Last 18

The lead change time in hours, the lead and last boiler
numbers and the mode (either Auto or Manual).

Manual:

Default = 100 hours

Password

19

Used to enter a password. This allows access to screens 20
through 34.

Default = AAA

To change: Screen 22

Unit Setup/

Network

20

Sets up the pump, boiler and stage configuration for the
System Monitor (Screen 11). Preset = 2 boilers / 4 stages.

Default =

PBSSSBSSSAAA
Note: See Table I

System Test

21

When ACTIVE, initiates auto system test and displays all
screens.

Default = Not Active

Set Password

22 Changes the current user password.

Default = AAA

Water

Temperature

Limits

23

Sets Maximum and Minimum water temperature limits
allowed by the user in the Water Temperature Screen

Min. Default = 105°F

(40.5°C), Max. Default =

210°F (98.8°C)

Master/Slave

Unit

24

Displays the number of sensors utilized, relays (stages or
boilers) and Aux contacts.

Default = Master

Slaves

Connected

25 Selects the number of slave units connected, if any.

Default = 00

LonWorks

26

If ON, the LonWorks network will be active.

Default = OFF

Factory Defaults 27 If YES selected, the factory defaults will be restored.

Default = NO

User Defaults

28

If YES is selected, the User Defaults can be stored or
invoked.

Default = None

Terminal

Password

29

Used to enter a password for modem operation.

Default = AAA

Alarm Call Tele 30

Modem system telephone number to be called when a fault
occurs.

None

Alarm Call ID

31

Modem system ID person or place to be called when a fault
occurs.

None

Alarm Call Retry 32 Modem system error call retries.

None

Alarm Call

Events

33 Modem system error indications.

None

PID Settings

34 Configures PID operation.

Default =

Interval = 05

KP = 06

KI = 05

KD = 01