www.schischek.com

Dimension size S

Specification

The "ME"-data sheet contains additional information for ExMax and

RedMax actuators of the size "S", for the optimization and simplification

in regard to planning, installation and initial start up. It provides

influences of external factors in reference to the safe initiation of

the actuators. In particular it represents the installation, as well as

different flabs, fire protection flabs and armatures. Additionally

describing different accessory elements and their mounting to the

actuator.

Specification

Schischek GmbH Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax ++49 (0)9101-908177, Email [email protected]

ExMax-.. and RedMax-.. extra information ME - size S

E X P L O S I O N P R O O F

u

Dimension, drill template

u

Control elements: switch - push button - LED

u

Outdoor installation

u

Mounting using form-fitting shaft connection (square shaft)

u

Mounting using clamp mounting (round shaft)

u

Mounting on butterfly valves and ball valves

u

Mounting on fire dampers

u

Mounting ExBox (RedBox), ExSwitch (RedSwitch)

Dimensions - drill template

Control elements: switch - push button - LED

Outdoor installation

Switch - push button - LED for programming,

behind dummy plug

10-position switch (S)

Push button (T)

3-colour LED

S

T

ExMax/RedMax - extra information ME

118,5

30

30

14

210

74

95

80

Dimension in mm

Side R

Side L

6 x Æ 4,4

6 x M 4

Double sqaured 12 x 12 mm

60

inl. radius

of bend for

the cable

All ExMax and RedMax actuators are equipped with a 10 position switch a push button

and a multicolor LED for calibration. These control elements are to be found cable-

laterally behind the two middle sectioned dummy plugs. For operation these must be

removed. The calibration can be achieved despide lining up tension at the actuator.

The explosion prevention is not impaired thereby. However it has to be of great concern

that the dummy plugs must be rescrewed in order to comply with the IP-protection

class. The operation of the switch and button has to be done by means of a small

screwdriver. Force with strong pressure and /or rotation is to be avoided in any case,

since otherwise control electronics can be damaged irreparably. By bad visibilities a

flashlight (certified within the EX-range) should be used. Attitudes of torque and running

time can be achieved also before mounting. The adjustment of angle of rotation can

be started only with an outside load and accurate mounting.

RST

When mounting actuator outdoors it has to be certain that the actuator is protected against

direct sun exposure (warmth and UV), rain and snow by employing an enclosure roof.

Supply voltage is to be applied immediately after mounting in order to assure integrated

heating at start. Since explosion proof actuators must have internal safety temperature

limiters, these may not be exposed neither at storage nor during operation to a too high

temperature. Otherwise the limiters could respond and switch of the actuator irreversibly.