www.schischek.com

Mounting instructions and important information for operation and installation

D.EM-03.08-S-en-BF

2006-06-14

Schischek GmbH Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax ++49 (0)9101-908177, Email [email protected]

RedMax-5.10-BF

RedMax-15-BF

Special makes

RedMax-..-VA/-CT

E X P L O S I O N P R O O F

Important information for installation and operation

Mounting of quarter turn valves

Mounting on air dampers with double squared shaft connection

RedSwitch - adaptable external EEx-d aux. switches

RedBox - adaptable terminal box

EEx-i safety temperature sensor - FireSafe

Extra information "EL" (see additional data sheet)

extra technical information, versions of circuit diagrams and failure indication

Extra information "ME" (see additional data sheet)

extra technical information, dimensions, installation instruction and illustration

Important information for routine test

A. Installation, commissioning, maintenance

The cable of the actuator must be installed in a fixed position and protected against

mechanical and thermical damage. In acc. with operation RedMax actuators are

maintenance free. Nevertheless maintenace must comply with regional standards,

rules and regulations. The actuators must not be opened by the customer. For outdoor

installation a protective housing against rain, snow and sun should be applied to the

actuator, as well as a constant supply at terminal 1 and 2 for the integral heater. For

electrical connection inside hazardous areas an terminal box is requested (e.g. type

RedBox).

Example: you have to cut the supply voltage before opening an EEx-e terminal box
B. Shaft connection, selection of running time, heater

RedMax actuators are equipped with a direct coupling double squared shaft connection

of 12 x 12 mm. For round shafts an adaptor is available (Accessory type KB-S).

The housing of the actuator is axially symmetrically built to select open/close direction

of the spring return function by left/right mounting.

In acc. to the actuator type 5 different motor running times and 2 different spring return

running times can be selscted on site. The integral heater is for ambient temperatures

down to -40°C.
C. Working with 3 sec. motor running time

See extra information “EL”.
D. 3-pos control mode

See extra information “EL”.
E. Spring return

Spring return function works if the supply voltage (terminal 1 or 2) is cut. In the event

of an electrical interruption, the spring returns to its end position.
F. Operation at an ambient temperature below - 20°C

See extra information “EL”.
G. Excess temperature

In acc. to the ATEX rules and regulations EEx actuators must be protected against

excess temperature. An internal thermostat guarantees the temperature class in the

event of failure. If this thermostat is working the actuator must be sent to the factory.

RedMax actuators are equipped with an additional temperature sensor to stop the

actuator before reaching this max. temperature. In this case the failure must be

eliminated immediately on site.

Details see extra information “ME”.

Details see extra information “ME”.

RedSwitch is an accessory to RedMax actuators size

S, fixing directly onto the actuator. RedSwitch are aux.

switches with with 2 potential free contacts, adustable

on site. The electrical wiring needs an terminal box.

For electrical connection of an RedMax inside the hazar­

dous area an terminal box is required.

RedBox-BF for RedMax-5.10-BF and RedMax-15-BF.

To adapt the RedBox direct to the actuator housing an

additional accessory type MKK-S is required.

The safety thermostat type FireSafe is passive and

potential free for use in intrinsic safe circuits, directly

connectable to the EEx-i circuit of the RedMax-...-BF

actuators. The sensor switches at an ambient temperature

of 72°C and starts the fail safe spring return function of

the actuator. Sensor with manufacturer certificate in acc.

with ATEX.

For periodic inspection of fire dampers cut of the the supply line (cut off the current

of the actuator)

The switch contact on FireSafe is only for test aims of actuators function.