Rear exit / horizontal termination – Napoleon Fireplaces BGD36PTR User Manual

Page 11

background image

11

W415-0210 / E / 06.25.03

See graph to determine the required vertical rise

V

T

for the

required horizontal run

H

T

For vent configurations requiring more than two 90° el-
bows the following formulas apply:

Formula 1:

H

T

< V

T

Formula 2:

H

T

+ V

T

< 40 feet

REQUIRED
VERTICAL
RISE IN
FEET
V

T

HORIZONTAL VENT RUN PLUS OFFSETS IN FEET

H

T

Example 4:

V

1

= 9 ft

V

2

= 6 ft

V

T

=

V

1

+

V

2

= 9 + 6 = 15 ft

H

1

= 3 ft

H

2

= 2 ft

H

3

= 1.5 ft

H

R

=

H

1

+

H

2

+

H

3

= 3 + 2 + 1.5 = 6.5 ft

H

O

= .03(four 90° elbows - 90°)

= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft

H

T

=

H

R

+

H

O

= 6.5 + 8.1 = 14.6 ft

H

T

+ V

T

= 14.6 + 15 = 29.6 ft

Formula 1:

H

T

< V

T

14.6 < 15

Formula 2:

H

T

+ V

T

< 40 feet

29.6 < 40

Since both formulas are met, this vent configuration is ac-
ceptable.

FIGURE 12

FIGURE 11

H

1

H

2

V

1

V

2

H

3

90°

90°

90°

90°

The shaded area within the lines represents acceptable
values for H

T

and V

T

.

REAR EXIT / HORIZONTAL TERMINATION

when

(H

T

) < (V

T

)

Simple venting configuration (only two 90° elbows)