beautypg.com

Accessories — condensing unit – Nordyne Outdoor Heat Pump T3BN User Manual

Page 14

background image

14

ACCESSORIES —

Condensing Unit

Low Ambient Kit 913549A- Maintains system
pressures during low ambient conditions.

PHYSICAL AND ELECTRICAL SPECIFICATIONS / OUTDOOR UNITS
10.1 EER —High Effi ciency — Three Phase

COPPER WIRE SIZE — AWG

(1% Voltage Drop)

Supply Wire Length-Feet

Supply Circuit

200

150

100

50

Ampacity

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Model No. T3BN-

090C

090W

120C

120W

Electrical Data

Volts-Phase-Hz

280/230-3-60

460-3-60

280/230-3-60

460-3-60

380/420-3-50

380/420-3-50

Voltage Range (Min-Max)

187-253

414-506

187-253

414-506

Total Amps

32.1

16.4

33.4

17.2

Min Circuit Ampacity

41.4

21.7

43

22.7

Delay Fuse Max. (1)

60

35

70

35

Wire Size/Max Length (AWG 60°C Cu)

4/100

8/100

4/100

8/100

Wire Size/Max Length (AWG 75°C Cu)

6/100

8/100

4/100

8/100

Component Data

Coil

Area (ft^2)

31.94

31.94

31.94

31.94

Rows-FPI

2-16

2-16

2-18

2-18

Tube Dia.

3/8” OD

3/8” OD

3/8” OD

3/8” OD

Fan Motor

Volts-Phase-Hz

280/230-3-60

460-3-60

280/230-3-60

460-3-60

380/420-3-50

380/420-3-50

Qty

1

1

1

1

Horsepower

3/4

3/4

3/4

3/4

Full Load Amps

3.3

1.7

3.3

1.7

Fan Blade

Dia./Pitch/#Blades

30/19/3

30/19/3

30/26/3

30/26/3

RPM/CFM (Max-Total)

825/7500

825/7500

825/8500

825/8500

Compressor
Data

Volts-Phase-Hz

280/230-3-60

460-3-60

280/230-3-60

460-3-60

Qty./Type

1 / Scroll

1 / Scroll

1 / Scroll

1 / Scroll

RLA

28.8

14.7

30.1

15.5

LRA

195

95

225

114

Stages/Percent

1 / 100

1 / 100

1 / 100

1 / 100

Crankcase Heater Qty./Type

1 / Band

1 / Band

1 / Band

1 / Band

Refrigerant Suction Line-Length/O.D.

0 - 15 ft.

1 1/8”

1 1/8”

1 1/8”

1 1/8”

(Liq. Line All Lengths - 5/8” O.D.)
Circuits (Qty) - 1

16 - 25 ft

1 3/8” (3)

1 3/8” (3)

1 3/8” (3)

1 3/8” (3)

26 - 75 ft.

1 3/8” (3)

1 3/8” (3)

1 3/8” (3)

1 3/8” (3)

Refrigerant Charge

Holding Charge

56

56

90

90

R-22 Ounces

Total System with 15’ Line Set (2)

374

374

486

486

Weight

Net

413

413

423

423

Approximate (lbs.)

Ship

425

425

435

435

(1) HACR Type Circuit Breakers may be used.
(2) Add 9.0 oz. of refrigerant per 5 feet of additional line set.
(3) Requires a 1-3/8” to 1-1/8” reducer line to unit.