beautypg.com

Nordyne Outdoor Heat Pump T3BN User Manual

Page 12

background image

12

REFRIGERANT CHARGING CHART
Heating Mode of Operation

PR

OCEDURE FOR CHARGING 10-T

ON HEA

T PUMP IN HEA

TING MODE.

1.

Ev

acuate the refr

iger

ant system.

2.

Charge the system b

y

w

eighing in 30 lbs R-22 refr

iger

ant.

This is the recommended charge f

or 5/8 inch 15 f

oot line set.

F

or line sets other than 15 f

eet add 9.0 oz.

R-22 per additional 5 f

eet of 5/8 inch liquid line o

v

er 15 f

eet and remo

v

e

9.0 oz

per 5 f

eet less than

15 f

eet of liquid line

.

3.

Ensure that the unit is oper

ating proper

ly per the heating functional chec

k

out in these installation instr

uctions

.

7.5

T

o

n

OUTDOOR

TEMPERA

TURE (DEG.

F)

0

1

0

2

03

04

0

5

0

6

0

Suc.

Liquid

Disc

h.

Suc.

Liquid

Disc

h.

Suc.

Liquid

Disc

h.

Suc.

Liquid

Disc

h.

Suc.

Liquid

Disc

h.

Suc.

Liquid

Disc

h.

Suc.

Liquid

Disc

h.

Press

Press.

T

emp.

Press.

Press.

T

emp.

Press.

Press.

T

emp.

Press.

Press.

T

emp.

Press.

Press.

T

emp.

Press.

Press.

T

emp.

Press.

Press.

T

emp.

19

134

135

20

140

135

21

146

136

22

152

136

32

162

157

51

199

198

61

248

179

20

141

133

21

146

133

22

151

134

23

156

134

33

169

154

52

206

193

62

255

185

21

148

131

22

152

131

23

156

132

24

160

132

34

176

151

53

213

189

63

262

191

22

155

129

23

158

129

24

160

130

25

163

130

35

183

148

54

220

184

64

269

198

23

162

127

24

163

127

25

165

128

26

167

128

36

190

146

55

227

180

65

276

204

24

169

125

25

169

125

26

170

126

27

171

126

37

197

143

56

234

175

66

283

210

25

176

123

26

175

123

27

175

124

28

174

124

38

204

140

57

241

171

67

290

216

*Note:

All pressures are listed in psig.

and all temper

atures in deg.

F

.

- Shaded Bo

x

es indicate fl

ooded conditions

- Rated Design

V

alues

. Suction Pressure will be lo

w

er than design

v

alue if indoor air fl

o

w

, enter

ing dr

y b

ulb

, or enter

ing w

et b

ulb

temper

atures are lo

w

er than design.

- Discharge temper

atures g

reater than char

ted v

alues indicates a

refr

iger

ant undercharge

.