Npi40 installation – Napoleon Fireplaces NPI40 User Manual

Page 19

background image

W415-0616 / C / 06.04.08

19

MINIMUM CLEARANCES TO COMBUSTIBLES

Side wall to unit

8"

Maximum mantel depth

10"

Mantel to top of unit

8"

Top facing to unit

6 3/8"

Side facing to unit

6"

Floor

protection*

6"*

* Floor Protection: Minimum 6" in front of door and to either
side.

MINIMUM MANTEL CLEARANCES

REAR TO TOP VENT CONVERSION INSTRUCTIONS

NOTE: The insert is factory shipped in a rear vent confi guration.

1. To vent exit vertically, remove the two screws holding the exhaust cover.

NOTE: Be careful not to damage the gasket.

2. Remove the two screws holding the exhaust tube

NOTE: Be careful not to damage the gasket.

3. Attach the exhaust tube and gasket in the vertical position.

4. Attach the exhaust cover and gasket over the horizontal exit.

Figure 18

Exhaust Tube

Exhaust Cover

Figure 20

Figure 19

NPI40 INSTALLATION