beautypg.com

Nortec ASD User Manual

Page 8

background image

- 6 -

C2

D

GO TO

Always align distributor holes so that steam is discharged
upwards to ensure condensate will remain in the distributor.

H

1/3W

2/3W

W

1/3W

1/3W 1/3W 1/3W

Min. W = 8” (203 mm)

Figure #5

Vertical Airflow

WARNING:

·

These installation guidelines apply for duct velocities under 2000 ft/min (610 m/min), please consult factory
for higher velocities.

·

Please make sure no obstacles (elbow, filter, or diffuser) are located after the distributor in the direction of the
airflow closer than the absorption distance calculated for your application.

·

Unless you know the exact absorption distance required for the steam absorption into the air stream, the
distributor should be located at least 8-10 ft (2-3 m) away from any obstacle it may condense on (elbow,
diffuser, filter, etc.).

This manual is related to the following products: