Installation, Distributor mounting, Vertical airflow – Nortec ASD User Manual
Page 3
INSTALLATION
RECEIVING & UNPACKING EQUIPMENT
1.
Check packing slip to ensure ALL material
has been delivered.
2.
All material shortages are to be reported to
Walter Meier (NORTEC) within 48 hours
from receipt of goods. Walter Meier
(NORTEC) assumes no responsibility for
any material shortages beyond this period.
3.
Inspect shipping boxes for damage and
note on shipping waybill accordingly.
4.
After unpacking, inspect equipment for
damage and if damage is found, notify the
shipper promptly.
5.
All NORTEC products are shipped on an
F.O.B. factory basis. Any and all damage,
breakage or loss claims are to be made
directly to the shipping company.
6.
Each distributor is provided with: installation
manual, one hose cuff, and two hose
clamps.
PRE-INSTALLATION CHECK
1.
Ensure the total capacity of the humidifier is
not higher than the allowable maximum
steam capacity of the distributors used.
ASD 10: 22 lbs/hr (8 kg/hr)
ASD: 25 lbs/hr (9 kg/hr)
BSD: 35 lbs/hr (13 kg/hr)
CSD: 115 lbs/hr (45 kg/hr)
STEAM LINE INSTALLATION
GUIDELINES
1.
Nortec steam hose should only be used on
short steam runs below 10 feet.
2.
Ensure that no condensate produced in the
steam line will remain trapped. Steam
naturally flows upward and condensate
naturally flows downward.
3.
See material recommended for use in the
chart below. To eliminate the metal
corrosion, Nortec does not recommend the
use of steel piping.
Chart #1
Steam Line Material
Steam
Hose
Copper Tube
Stainless
Steel Tube
Short run
< 10 feet
(3 m)
ь
ь
ь
Long run
> 10 feet
(3m)
ь
ь
DI / RO
water
ü
4.
Consult the following pages for step by step
distributor installation starting with Figure
#1.
5.
Consult the charts below for steam and
condensate sizing guidelines when using
steam distributors.
Chart #2
Recommended material and size for steam run
- 1 -
lb/hr
kg/hr
ft
m
0-30
0-13
0-10
0-3
Copper
tube
3/4" MED-L Tubing
(7/8" O.D.)
0-30
0-13
10 +
3 +
Copper
tube
1” MED-L Tubing
(1 1/8" O.D.)
0-30
0-13
0-10
0-3
Stainless
Steel tube
7/8” tube x
0.049” thick.
0-30
0-13
10 +
3 +
Stainless
Steel tube
1 1/8” tube x 0.049”
thick.
30-100
13-45
0-20
0-6
Copper
tube
1 ½” MED-L Tubing
(1 5/8" O.D.)
30-100
13-45
20 +
6 +
Copper
tube
2” MED-L Tubing
(2 1/8" O.D.)
30-100
13-45
0-20
0-6
Stainless
Steel tube
1 ¾” tube x
0.065” thick.
30-100
13-45
20 +
6 +
Stainless
Steel tube
2” tube x
0.065” thick.
Load
Steam Run
Steam
Line
Material
Steam Line
Description
Please note that options shown in a bold-italic font requires
that reducers be used at both ends. These extra large sizes are to
allow for better condensation removal in long steam runs. These
sizes will not permit you to use hose coupling to connect your
self to either humidifier or distributors.