Model 200erv, Performance, Dimensions 200erv – Lifebreath MAXTOP User Manual
Page 14: Engineering data

14
OPTIONS
99-104
Digital Electronic Timer - 20/40/60 min. (3 wire)
99-109
Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-186
Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen
WARRANTY
Units carry a 5 year warranty on the energy recovery core and
replacement parts.
ERVs are not recommended for regions where the design tempera-
ture is below 25°F (-4°C)
STALE AIR
TO OUTSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FRESH AIR
TO INSIDE
14
3
/
4
"
(375)
19"
(483)
*
All Duct Connections 6"(150mm)
FILTERS
BLOWERS
*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for ser vicing unit.
MOTOR
ENTHALPIC CORE
33-5/8"
(850)
BALANCING
DAMPER
BALANCING
DAMPER
Model 200ERV
DIMENSIONS 200ERV
inches (mm)
TI-98E
0107
ENGINEERING DATA
LATENT RECOVERY/MOISTURE TRANSFER CORE
The cross-flow energy recovery core transfers heat and water vapour
between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC
motor. 5 speed fan operation. High speed - 120 VAC.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE ERV
Four threaded inserts at corners of case designed to accept four PVC
reinforced polyester straps that are supplied with the unit.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated to prevent exterior condensation.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has
5 speeds). Control pad can be removed from HRV and remotely mounted.
Weight 63 lbs. (28.7 kg)
Shipping Weight 65 lbs. (29.6 kg)
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
All units conform to
CSA and UL standards.
1
2
3
20
40
60
80
100
120
140
160
180
200
220
240
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Static Pressure (in w.g.)
A
ir
Flow (
c
fm
)
3 - High Speed
2 - Medium Low Speed
1 - Low speed
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure)
[cfm (L/s)]
@ 0.1" (25 Pa)
214 (101)
@ 0.2" (50 Pa)
206 (97)
@ 0.3" (75 Pa)
193 (91)
@ 0.4" (100 Pa)
184 (87)
@ 0.5" (125 Pa)
170 (80)
@ 0.6" (150 Pa)
155 (73)
@ 0.7" (175 Pa)
137 (65)
Sensible Effectiveness
@ 127 cfm (60 L/s)
32°F (0°C)
67%
*Sensible Efficiency
@ 127 cfm (60 L/s)
32°F (0°C)
60%
Total Efficiency
55%
VAC @ 60HZ
120
WATTS / Low speed.
70
WATTS / High speed
182
Amp rating
1.4