Model 300dcs, Performance, Engineering data – Lifebreath MAXTOP User Manual
Page 13: Dimensions 300dcs

OPTIONS
99-104
Digital Electronic Timer - 20/40/60 min.
99-109
Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad.
99-250
Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.
99-160
Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 7”
(178 mm)
99-161
Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 7”
(178 mm)
99-186
Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5
year replacement parts warranty.
13
49 "
(1245)
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
14 3/4"
(375)
19"
(483)
Por ts
7" (178 mm)
CONDENSATE
DRAINS
BLOWERS
*NOTE: Front clearance of 25 inches (635 mm)
is recommended for ser vicing unit.
MOTOR
FRESH AIR
FROM OUTSIDE
STALE AIR
FROM INSIDE
FILTER
DEFROST
DAMPER
DEFROST AIR
FROM INSIDE
FILTER
Por ts
6" (150 mm)
METAL CLASPS
TI-102-NE
0107
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams.
The two cores are arranged for highly efficient counter current airflow.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor.
5 speed fan operation. 120 VAC, 2.9 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced
polyester straps that are supplied with the unit.
DEFROST
Damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis-
tance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2"
(12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode (each mode has 5
speeds). Control pad can be removed from HRV and remotely mounted.
Weight 106 lbs. (48 kg)
Shipping Weight 108 lbs. (49 kg )
Model 300DCS
DIMENSIONS 300DCS
inches (mm)
Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
All units conform to
CSA and UL standards.
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency – takes into account all power inputs
Performance
(HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure)
[cfm (L/s)]
@ 0.1" (25 Pa)
265 (125)
@ 0.2" (50 Pa)
260 (123)
@ 0.3" (75 Pa)
250 (118)
@ 0.4" (100 Pa)
235 (111)
@ 0.5" (125 Pa)
220 (104)
@ 0.6" (150 Pa)
203 (96)
@ 0.7" (175 Pa)
186 (88)
@ 0.8" (200 Pa)
167 (79)
Max. Temperature Recovery
90%
Sensible Effectiveness
@ 119 cfm (56 L/s)
32°F (0°C)
90%
*Sensible Efficiency
@ 119 cfm (56 L/s)
32°F (0°C)
79%
*Sensible Efficiency
@ 125 cfm (59 L/s)
-13°F (-25°C)
75%
VAC @ 60HZ
120
WATTS / Low speed.
150
WATTS / High speed
333
Amp rating
2.9
1
2
3
4
5
60
80
100
120
140
160
180
200
220
240
260
280
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Static Pressure (in w.g.)
Ai
r F
lo
w
(
c
fm
)
5 - High Speed
*4 - Medium High Speed
*3 - Medium Speed
*2 - Medium Low Speed
*1 - Low speed
* Manufacturers Data