CERTIFIED TEST DATA
HVI-2100 CERTIFIED RATINGS comply with new
testing technologies and procedures prescribed by the
Home Ventilating Institute, for off-the-shelf products, as
they are available to consumers. Product performance is
rated at 0.1 in. static pressure, based on tests conducted in
AMCA's state-of-the-art test laboratory. Sones are a
measure of humanly-perceived loudness, based on
laboratory measurements. This NuTone model is listed by
Underwriters' Laboratories Inc.
The air delivery of a ventilating system may be
determined by:
1. Determine the equivalent duct length for each 90 degree
elbow by adding one foot of duct length for each inch of
duct diameter, i.e., a 4 inch diameter duct elbow equals
4 feet equivalent duct length and an 8 inch diameter
duct elbow equals 8 feet equivalent duct length.
2. Add the total straight length of duct and the equivalent
length for each elbow to obtain the total equivalent
duct length.
3. Locate the intersection of the fan performance curve and
the total equivalent duct length curves and draw a
vertical line down to the CFM scale and read the system
air performance.
(NOTE: 3
1
⁄
4
" x 10" duct equals 6 inch diameter duct.)
100
50
0
0.00
0.10
0.20
0.30
0.40
0.50
ST
A
TIC PRESSURE–INCHES OF W
A
TER
50 Feet
40 Feet
30 Feet
20 Feet
10 Feet
CFM CUBIC FEET PER MINUTE
75
125
25
AIR PERFORMANCE CURVE
(4 In. Duct to 10 Foot Lengths)
STATIC PRESSURE
INCHES OF WATER
CFM
0.05
77
75
72
70
67
64
60
54
47