CAUTION: When sizing the wire, you must follow the guidelines of the
latest revision of the NEC. NM-B wire is equivalent to “Romex” cable. SEU
is equivalent to service entry cable. For NEC type NM-B wire, you must
size the wire using 60C ratings per NEC article 326.

* Minimum overcurrent protection per NEC 424-3b not to be less than 125%

of total amps for fi xed resistance heat.

Table 9a. Electrical Specifi cations

** Alternate wiring combinations can be used. Refer to the latest revision of the NEC for these

appropriate alternate combinations.

Table 9b. Recommended Electrical Application Guide

for Dual Circuit Installations**

Model

Number

E3E(*)

Supply

Circuit

Total

Amperes

Maximum

Over-current

Rating

Minimum

Circuit

Ampacity

Copper Wire Size - See

Caution Below

Ground

Wire

Size

Low

Voltage

Thermostat

Wire Size

60°C

(e.g., Romex)

90°C

(e.g., SEU)

-010H

Single

45.5

60

57

4

6

10

2-Wire system
maximum wire

lengths:

24 Ga.= 55'
22 Ga.= 90'

20 Ga.= 140'
18 Ga.= 225'

-012H

Single

52.1

70

65

4

6

8

Dual "A"

28.0

40

35

8

8

10

Dual "B"

24.2

30

30

10

10

10

-015H

Single

66.3

90

83

2

4

8

Dual "A"

45.5

60

56

4

6

10

Dual "B"

20.8

30

26

10

10

10

-017H

Single

71.3

90

89

2

4

8

Dual "A"

48.8

60

60

4

6

10

4 or more

Wire systems

maximum wire

lengths:

24 Ga.= 25'
22 Ga.= 45'
20 Ga.= 70'

18 Ga= 110'

Dual "B"

22.5

30

28

10

10

10

-020H

Single

87.1

125

109

0

2

6

Dual "A"

45.5

60

57

4

6

10

Dual "B"

41.7

60

52

4

6

10

-023H

Single

93.8

125

117

0

2

6

Dual "A"

52.1

60

60

4

6

10

Dual "B"

41.7

60

56

4

6

10

Model

Number

E3EX

Supply

Circuit

Total

Amperes

Maximum

Over-current

Rating

Minimum

Circuit

Ampacity

Copper Wire Size - See

Caution Below

Ground

Wire

Size

Low

Voltage

Thermostat

Wire Size

60°C

(e.g., Romex)

90°C

(e.g., SEU)

-010

Single

47.7

60

57

4

6

10

2-Wire system
maximum wire

lengths:

24 Ga.= 55'
22 Ga.= 90'

20 Ga.= 140'
18 Ga.= 225'

-012

Single

54.3

70

67

4

6

8

Dual "A"

30.2

40

35

8

8

10

Dual "B"

24.2

30

30

10

10

10

-015

Single

66.0

90

83

2

4

8

Dual "A"

46.0

60

57

4

6

10

Dual "B"

20.0

30

25

10

10

10

-017

Single

71.5

90

89

2

4

8

4 or more

Wire systems

maximum wire

lengths:

24 Ga.= 25'
22 Ga.= 45'

Dual "A"

51.0

60

60

4

6

10

Dual "B"

22.5

30

28

10

10

10

-020

Single

86.0

125

109

0

2

6

Dual "A"

46.0

60

57

4

6

10

Dual "B"

40.0

60

50

4

6

10

Replacement furnace for E2E(*)-015HB

E2E(*)-

015HBR

Single

67.1

90

83

2

4

8

Replacement

furnace for

E2E(*)-015HB

Dual "A"

35.5

50

44

6

8

10

Dual "B"

31.7

40

39

8

8

10

Circuit "A"

Circuit "B"

Model Number

E3E(*)

Wire Gauge

and Type

Breaker

Size

Wire Gauge

and Type

Breaker

Size

-012H

#8 NM-B

40 amp

#10 NM-B

30 amp

-015H

#6 SEU

60 amp

#10 NM-B

30 amp

-017H

#6 SEU

60 amp

#10 NM-B

30 amp

-020H

#6 SEU

60 amp

#6 SEU

60 amp

-023H

#6 SEU

60 amp

#6 SEU

60 amp

Replacement furnace for E2E(*)-015HB

E2E(*)-015HBR

#8 SEU

50 amp

#8 NM-B

40 amp