NEC 500 UPS Uninterruptible N8580-31 User Manual

Page 14

background image

11

11. Maintenance and Checks

Storage
Storage Conditions

Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at
least 4 hours.

Extended storage

At -15 to +30

°

C (+5 to +86

°

F), charge the UPS’s battery every 6 months.

At +30 to +45

°

C (+86 to +113

°

F), charge the UPS’s battery every 3 months.

Daily Check
Check the front bezel LEDs and the temperature of the room in which the UPS resides.

Scheduled Check
Once a year check the UPS for discoloration anywhere, frayed cables or power cords, or other signs of deterioration. Check that
the air flow around the UPS is adequate and that the vent is clear.

Battery Life

Temperature

Battery Life

Change Battery After

20

°

C

5 years

4.5 years

30

°

C

4 years

3.5 years

40

°

C

2.5 years

2 years