N-Tron 400 User Manual
Page 11

Rev 102507
11
N-TRON SWITCH GROUNDING TECHNIQUES
The grounding philosophy of any control system is an integral part of the design. N-Tron switches are designed 
to be grounded, but the user has been given the flexibility to float the switch when required. The best noise 
immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via 
a drain wire. Some N-Tron switches have metal din-rail brackets that can ground the switch if the din-rail is 
grounded. In some cases, N-Tron switches with metal brackets can be supplied with optional plastic brackets if 
isolation is required. 
 
Both V- legs of the power input connector are connected to 
chassis internally on the PCB. Connecting a drain wire to 
earth ground from one of the V- terminal plugs as shown here 
will ground the switch and the chassis. The power leads from 
the power source should be limited to 3 meters or less in 
length. 
 
As an alternate, users can run a drain wire & lug from any of the Din-Rail 
screws or empty PEM nuts on the enclosure. When using an unused PEM 
nut to connect a ground lug via a machine screw, care should be taken to 
limit the penetration of the outer skin by less than 1/4 in. Failure to do so 
may cause irreversible damage to the internal components of the switch. 
 
Note: Before applying power to the grounded switch, you must use a volt 
meter to verify there is no voltage difference between the power supply’s 
negative output terminal and the switch chassis grounding point. 
 
The use of shielded cables between devices is not required for most N-Tron devices (please consult the user 
manuals for specific details). If the use of shielded cables is required, it is generally recommended to only 
connect the shield at one end to prevent ground loops and interfere with low level signals (i.e. thermocouples, 
RTD, etc.). Cat5e cables manufactured to EIA-568A or 568B specifications are required for use with N-Tron 
Switches. 
 
In the event all Cat5e patch cable distances are small (i.e. All Ethernet devices are located the same local 
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to 
chassis ground at both ends in systems void of low level analog signals. 
 
