ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
- Each air stream has one centrifugal
blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.4 Amps.
FILTERS
- Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
- Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are supplied
with the unit.
DEFROST
- Recirculating damper defrost system.
DEHUMIDISTAT
- Adjustable Internal Dehumidistat.
CASE
- Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS
- ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode,
Recirculation mode, (each mode has 5 speeds). Control pad
can be removed from HRV and remotely mounted.
WEIGHT 87 lbs. (39.5 kg) SHIPPING WEIGHT 89 lbs. (40.5 kg)
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
196
(93)
@ 0.2” (50 Pa)
188
(89)
@ 0.3” (75 Pa)
178
(84)
@ 0.4” (100 Pa)
165
(78)
@ 0.5” (125 Pa)
149
(71)
Maximum Temperature Recovery
80%
Sensible Effectiveness
@ 117 cfm (55 L/s )
(CSA C439M)
72%
Sensible Efficiency
@ 117 cfm (55 L/s) 32
O
F (0°C)
64%
Sensible Efficiency
@ 67 cfm (31 L/s) -13
O
F (-25°C)
70%
VAC @ 60HZ
120
WATTS / Low speed
74
WATTS / High speed
164
Amp rating
1.4
TOP VIEW
SIDE VIEW
25 1/2 "
(648 mm)
26 1/2"
(673 mm)
22 1/2"
(572 mm)
FRONT VIEW
ALL DUCT CONNECTIONS
ARE 6" (150 mm)
18"
(457 mm)
7 1/2"
(191 mm)
SUPPLY OF
FRESH AIR
FRESH AIR
SUPPLY
TO BUILDING
STALE AIR
RETURN FROM
BUILDING
STALE AIR
EXHAUST
DRAIN
CONNECTION
CONTROLS
*Service Clearance
25" (635 mm)
OPTIONS
99-104
Digital Electronic Timer - 20/40/60 min.
99-105
Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109
Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250
Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad
99-163
Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150mm)
99-164
Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150mm)
99-186 Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recov-
ery core and a 5 year replacement parts warranty.
TI-100-NE
1203
MAXTOP FANCURVE
200
150
175
75
50
100
125
25
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Air Flo
w
(cfm)
Static Pressure (inH
2
0)
HIGH SPEED
*
MEDIUM HIGH SPEED
MEDIUM SPEED
MEDIUM LOW SPEED
LOW SPEED
4
5
3
2
1
4
3
2
1
5
*
Manufacturers Data
Model MAXTOP
All units conform to
CSA and UL standards.
DIMENSIONS MAXTOP
inches (mm
)
511 McCormick Blvd.
270 Regency Ridge,
Suite 210
London, Ontario N5W 4C8
Dayton, Ohio 45459
T (519) 457-1904
T (937) 439-6676
F (519) 457-1676
F (937) 439-6685
Email: [email protected] Website: www.lifebreath.com