Model 200max, Options, Performance – Lifebreath 95MAX User Manual
Page 7: Dimensions 200max, Engineering data

7
BALANCING DAMPER
33 5/8"
(850mm)
STALE AIR
FROM INSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
14 3/4"
(375)
19"
(483)
*All Duct Connections 6" (150mm)
CONDENSATE DRAINS
FILTERS
BLOWERS
*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.
RECIRCULATING
DEFROST
DAMPER
MOTOR
CORE
OPTIONS
99-104
Digital Electronic Timer - 20/40/60 min.
99-105
Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109
Air Sentry™ Air Quality Monitor designed to accept remotely
mounted Control Pad
99-250
Ventilation Dehumidistat - Dehumidistat designed to accept
remotely mounted Control Pad.
99-163
Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150mm)
99-164
Duct Heater w/ Electronic SCR Thermostat, 2 Kw,
6” (150mm)
99-186
Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
WARRANTY Units carry a LIFETIME warranty on the heat recovery core
and a 5 year replacement parts warranty.
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P
cfm
L/s
@ 0.1” (25 Pa)
232
(109)
@ 0.2” (50 Pa)
223
(105)
@ 0.3” (75 Pa)
215
(102)
@ 0.4” (100 Pa)
195
(92)
@ 0.5” (125 Pa)
189
(89)
Maximum Temperature Recovery
81%
Sensible Effectiveness
@ 117 cfm (55 L/s)
(CSA C439M)
74%
Sensible Efficiency
@ 117 cfm (55 L/s) 32˚F (0˚C)
65%
Sensible Efficiency
@ 117 cfm (55 L/s) -13˚F (-25˚C) 66%
VAC @ 60HZ
120
WATTS / Low speed
87
WATTS / High speed
164
Amp rating
1.4
TI-99-NE
1203
200MAX FANCURVE
245
220
195
170
145
120
95
70
45
0.1
0.2
0.3
0.4
0.5
0.6
0.7
Air Flo
w
(cfm)
Static Pressure (inH
2
0)
5
4
3
2
1
HIGH SPEED
MEDIUM HIGH SPEED
MEDIUM SPEED
MEDIUM LOW SPEED
LOW SPEED
4
5
3
2
1
Model 200MAX
DIMENSIONS
200MAX
inches (mm
)
All units conform to
CSA and UL standards.
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC
motor. 5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four rein-
forced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation
mode, (each mode has 5 speeds). Control pad can be removed from
HRV and remotely mounted.
WEIGHT 71 lbs. (32.5 kg SHIPPING WEIGHT 73 lbs. (33.5 kg)
511 McCormick Blvd.
270 Regency Ridge,
Suite 210
London, Ontario N5W 4C8
Dayton, Ohio 45459
T (519) 457-1904
T (937) 439-6676
F (519) 457-1676
F (937) 439-6685
Email: [email protected] Website: www.lifebreath.com