4.4.4.4 TYPE MX341 AVR
The following 'jumper' connections on the AVR should be
checked to ensure they are correctly set for the generating set
application.
Refer to Fig. 4 for location of setting links.
1. Frequency selection terminals
50Hz operation LINK 2-3
60Hz operation LINK 1-3
2. Stability selection terminals
Frame UC22 LINK A-C
Frame UC27
LINK B-C
3. Sensing selection terminals *
LINK
2-3
LINK
4-5
LINK
6-7
4. Excitation Interruption Link
LINK
K1-K2
Fig. 4
4.4.4.5 TYPE MX321 AVR
The following 'jumper' connections on the AVR should be
checked to ensure they are correctly set for the generating set
application.
Refer to Fig. 5 for location of setting links.
Fig. 5
1. Frequency selection terminals
50Hz operation
LINK 2-3
60Hz operation
LINK 1-3
2. Stability selection terminals
Frame UC22
LINK A-C
Frame UC27
LINK B-C
3. Terminals K1 - K2
Excitation circuit breaker closed.
If this option not fitted, K1 - K2 linked at auxiliary terminal
block.