8 technical data – Philips SPB4230WA/17 User Manual
Page 16
16
16
8 Technical data
Input Maximum capacity
1440VA
Voltage
100-120V* +/-25% at line input
Current
12A
Frequency
50 or 60Hz* +/-10% (auto sensing)
Output Capacity
1000VA
Voltage (on battery) Simulated sine wave
at 100V/115V +/-5%
Frequency (on battery) 50 or 60Hz*
+/-1Hz
Auto Voltage Regulation AVR automati-
cally increases output voltage
(AVR function)
15% above input voltage if -9% to -25% of
nominal.
AVR decrease output voltage 13% below
input voltage
If +/-9% to +25% of nominal
Transfer time
2/4 milliseconds, including detection time
Protection and filtering
Spike protection
5100 joules, 2ms
Overload protection UPS automatically
shuts down if overload exceeds 120%
of nominal at 30 seconds and 130% at 3
seconds
Unit input
Fuse or circuit breaker for overload and
short circuit protection
Short circuit
UPS output cut off immediately or input
fuse protection
BatteryType
Sealed, maintenance-free lead acid
Recharge time
6 hours typically (to 90% of full capacity)
Protection
Automatic self test and discharge
protection
Quantity of batteries
1
DC voltage
12V (DC)
Dimension: Main unit
Net weight
22.7lbs (10.3Kg)
Dimensions WxDxH
16.93” x 12.7” x 3.74”
(mm) (430 x 323 x 95)