Burner setup & boiler operation – PB Heat EC Series User Manual
Page 18
![background image](/manuals/184765/18/background.png)
16
BURNER SETUP & BOILER OPERATION
CARLIN BURNER SPECIFICATIONS
Boiler
Model No.
Firing Rate
Burner
Model No.
Air
Shutter
Nozzle Size
Pump
Pressure
Start-up Settings
Air Band
Head Bar
EC/ECT-03-075
.75
EZ-1HP
Blank
0.60 70° B DEL³
150 psig
0.55
0.60 - 0.65
EC/ECT-03-100
1.00
EZ-1HP
Blank
0.85 70° A DEL
150 psig
0.65
0.85 - 1.00
EC/ECT-03-120
1.20
EZ-1HP
Blank
1.00 70° A DEL³
150 psig
0.80
0.85 - 1.00
Boiler
Model No.
Burner
Model No.
Air
Shutter
Nozzle Size
Pump
Pressure
Start-up Settings
Head Dim. A
Air Band
EC/ECT-04-125
99FRD
Blank
1.00 x 70° B DEL³
150 psig
2
40% open
EC/ECT-04-150
99FRD
Blank
1.25 x 60° B DEL³
150 psig
3
60% open
EC/ECT-04-175
99FRD
Blank
1.50 x 60° B DEL
150 psig
4
100% open
EC/ECT-05-175
99FRD
Open
1.50 x 60° B HAGO³
150 psig
5
10% open
EC/ECT-05-200
99FRD
Open
1.65 x 60° B HAGO
150 psig
5
45% open
EC/ECT-05-250
99FRD
Open
2.00 x 60° B HAGO³
150 psig
8
100% open
EC/ECT-06-275
102CRD
Open
2.25 x 60° B DEL³
150 psig
6
100% open
EC/ECT-06-300
102CRD
Open
2.50 x 60° B DEL
150 psig
8
100% open
BECKETT BURNER SPECIFICATIONS (140 psig Pump Pressure)
Boiler
Model No.
Burner
Model No.
Burner Head
Static Plate
Nozzle Size
Start-up Settings
Head Setting
Air Shutter
Air Band
EC/ECT-03-075
AFG-L1¹
L1¹
3-3/8"
0.65 60° B HAGO³
9.0
2
N/A
EC/ECT-03-100
AFG-L1
L1
3-3/8"
0.85 60° B HAGO
10.0
1
N/A
EC/ECT-03-120
AFG-L1
L1
—²
1.00 60° B HAGO³
9.0
2
N/A
EC/ECT-04-125
AFG-F6
F6
2-3/4"
1.10 80° A DEL³
5.0
1
N/A
EC/ECT-04-150
AFG-F6
F6
2-3/4"
1.25 80° B HAGO
8.0
1
N/A
EC/ECT-04-175
AFG-F6
F6
2-3/4"
1.50 80° B HAGO³
10.0
3
N/A
EC/ECT-05-175
AFG-MV1
M-V1-3
—
1.50 60° B HAGO³
10.0
3
3
EC/ECT-05-200
AFG-MV1
M-V1-3
—
1.75 60° B HAGO
10.0
9
3
EC/ECT-05-250
AFG-MV1
M-V1-5
—
2.00 45° B HAGO³
10.0
5
5
EC/ECT-06-275
CF-375
L1-S
—
2.25 45° P HAGO³
10.0
6
2
EC/ECT-06-300
CF-375
L1-S
—
2.50 45° P HAGO
10.0
6
3
RIELLO BURNER SPECIFICATIONS
Boiler
Model No.
Firing Rate
Burner
Model No.
Nozzle Size
Pump Pressure
Start-Up Settings
Turbulator
Air Damper
EC/ECT-03-075
.75
F5
0.60 60° B DEL³
155 psig
0.5
2.1
EC/ECT-03-100
1.00
F5
0.85 60° W DEL³
145 psig
2.0
2.6
EC/ECT-03-120
1.20
F5
1.00 60° W DEL
145 psig
3.0
2.9
EC/ECT-04-125
1.25
F5
1.00 60° W DEL
155 psig
2.5
3.4
EC/ECT-04-150
1.50
F10
1.25 60° B DEL³
145 psig
1.5
3.1
EC/ECT-04-175
1.75
F10
1.35 60° B DEL
165 psig
2.0
2.5
EC/ECT-05-175
1.75
F10
1.35 60° B DEL³
165 psig
2.0
2.5
EC/ECT-05-200
2.00
F10
1.50 60° B DEL
170 psig
2.5
2.8
EC/ECT-05-250
2.50
F10
2.00 60° B DEL³
155 psig
3.5
4.2
EC/ECT-06-275
2.75
F10
2.25 60° B DEL³
150 psig
4.0
4.2
EC/ECT-06-300
3.00
F10
2.50 60°B DEL
145 psig
4.5
4.2
Table 5.1:
Carlin Burner Specifications
Table 5.2:
Beckett Burner Specifications
Table 5.3:
Riello Burner Specifications
Factory Installed Nozzles (Packaged Boilers or Burner Cartons) are indicated in Boldface.
1 Requires Low Firing Rate Baffle
2 Remove Static Plate for 1.20 GPH Rate
3 Shipped Loose with Packaged Boiler or Burner Carton