Plantronics DYNZ-600 Series User Manual
Page 6

F-23371
Electronic Speed Switch Technical Manual
Page 4
2002 Invensys. All Rights Reserved
requirements. If set/trip point of SW1 is correct it is 
properly calibrated. If set/trip point is incorrect, go to 
step 5.3.2, 5.3.3 and 5.3.4 and calibrate unit. 
 
5.4 CALIBRATION OR CHECKING PROCEDURE 
FOR OS-SW2 TRIP POINT 
5.4.1 With no power applied to unit, connect an 
ohmmeter to terminals 7 and 9 (no other wires 
attached). The ohmmeter should indicate zero 
resistance (short circuit). This is the normally closed 
contact on relay OS-SW2. 
 
5.4.2 Apply correct DC power to terminals 1 and 2 of 
speed switch. 
 
The ohmmeter connected to terminals 7 to 9 should 
now indicate infinite resistance (open circuit). 
Originally the signal generator frequency was set 
below the units set/trip point (see step 5.2.2); 
therefore, it must change states when power is 
applied. 
 
 
 
 
5.4.3 Adjust the signal generator frequency to the 
desired OS-SW2 set/trip point as specified or 
calculated in step 5.2.1. 
 
5.4.4 Slowly turn the OS-SW2 potentiometer 
adjustment counterclockwise until the ohmmeter 
indicates an open circuit. This gives you the correct 
setpoint for OS-SW2. Remember OS-SW2 latches. 
 
5.4.5 Slowly increase the signal generator frequency 
until the ohmmeter connected to terminals 7 to 9 
indicates an open circuit. Note the frequency and 
verify that it is correct for your OS-SW2 set/trip point 
requirements. If set/trip point of OS-SW2 is correct it 
is properly calibrated. If set/trip point is incorrect, go to 
step 5.4.2, 5.4.3 and 5.4.4 and calibrate unit. 
 
6.0 OPERATION AND CALIBRATION OF 
DYNZ-60012 AND DYNZ-60013 SPEED 
SWITCH 
6.1 OPERATING PROCEDURE 
Once the system has been wired, the SPEED 
SWITCH functions in the following manner. 
 
6.1.1 No power applied to unit. 
l
SW1 and OS-SW2 relays are de-energized;
therefore, contacts are in position as shown on top of 
unit. 
 
6.1.2 Power is applied to unit when POWER SWITCH 
is turned on and no input signal to speed switch. 
l
SW1 relay remains de-energized; therefore, its
contacts remain in same position as those shown on 
top of unit. 
l
OS-SW2 relay remains de-energized; therefore, its
contacts remain in the same position as shown on top 
of unit. 
 
6.1.3 When the engine is cranked and the engine 
starts, SW1 energizes (non-latching) at its crank-
dropout trip point setting which is normally set to trip 
midway between the cranking RPM and idle RPM of 
the engine. 
 
6.1.4 When an overspeed condition occurs, OS-SW2 
relay energizes and it will remain energized until the 
frequency falls below the trip point at which time the 
relay will de-energize (relay is non-latching with no 
hysteresis). The engine over-speed setpoint is 
normally adjusted to trip at 10 to 20% above the 
engine operating speed. 
 
6.2 CALIBRATION PROCEDURE 
Equipment Required: Signal generator 
Frequency counter Ohmmeter 
 
6.2.1 Determine the desired trip points for your unit 
when using a magnetic pickup (MPU). 
 
No. of Gear Teeth x
Trip Point in Hz = Engine RPM Trip Point
60
 
6.2.2 Connect the signal generator and counter to 
terminals 5 and 6 with terminal 5 being the ground 
terminal. Set the signal generator frequency 100 Hz 
below the SW1 or OS-SW2 trip point you are trying to 
calibrate/set or check. Then adjust the out signal from 
the signal generator to 1 volt rms or greater. 
 
 
 
 
6.2.3 If you are calibrating unit, turn the desired trip 
point potentiometer adjustment 4 or 5 turns clockwise. 
 
6.3 CALIBRATION OR CHECKING PROCEDURE 
FOR SW1 TRIP POINT 
 
6.3.1 With no power applied to unit, connect an 
ohmmeter to terminals 10 and 12 (no other wires 
attached). The ohmmeter should indicate zero 
resistance (short circuit). This is the normally closed 
contact on relay SW1. 
 
6.3.2 Apply correct DC power to terminals 1 and 2 of 
speed switch. The ohmmeter connected to terminals 
10 to 12 should still indicate zero resistance, because 
you should be below the trip point for SW1 and it 
should not change states when power is applied to 
the unit. 
 
 
 
 
 
NOTE
If you are only checking calibration point, omit steps 
5.4.3 and 5.4.4 and go to step 5.4.5. 
NOTE
If you are only checking calibration point, omit steps 
6.3.3 and 6.3.4 and go to step 6.3.5. 
NOTE
Omit/skip step 6.2.3 if you are only checking the 
calibration points of the unit. 
Uncontrolled Document
For
H
istorical
Reference Only
