Electronic Speed Switch Technical Manual

Page 1

2002 Invensys. All Rights Reserved

1.0 INTRODUCTION

The Barber-Colman two setpoint speed switch
normally obtains its input signal from a magnetic
pickup which is positioned in proximity to the teeth of
a gear on a rotating shaft. The pickup generates an
AC signal voltage whose frequency is directly
proportional to the rate at which the gear teeth pass
by the pole piece. The speed switch converts the
input signal voltage into a DC signal which is
compared to the preset levels (setpoints) and actuate
the relays when the input signal frequency exceeds
the preset values.








1.1 APPLICATION

l

Overspeed Protection Signal

l

Underspeed Protection Signal

l

Crank Termination Signal

l

Generator Field Flashing Signal

l

Ignition Signal

l

Sequencing Signal

l

Tach Signal for Driving Model 40 Tachometer






1.2 RELAY LOGIC TABLE FOR SPEED SWITCHES

Switch

Power to Unit

and Input Signal

Frequency

below Trip Point

Power to Unit and

Input Signal

Frequency above Trip

Point

DYNZ-60010
SWl Relay
Contacts

De-energized
10 to 12 closed
11 to 12 open

Energized (non-
latching)
10 to 12 open
11 to 12 closed

DYNZ-60010
OS-SW2
Relay
Contacts

Energized
7 to 9 open
8 to 9 closed

De-energized (latched)
7 to 9 closed
8 to 9 open

DYNZ-60012
SW1 Relay
Contacts

De-energized
10 to 12 closed
11 to 12 open

Energized (non-
latching)
10 to 12 open
11 to 12 closed

DYNZ-60012
OS-SW2
Relay
Contacts

De-energized
7 to 9 closed
8 to 9 open

Energized (non-
latching)
7 to 9 open
8 to 9 closed

DYNZ-60013
SW1 Relay
Contacts

De-energized
10 to 12 closed
11 to 12 open

Energized (non-
latching)
10 to 12 open
11 to 12 closed

DYNZ-60013
OS-SW2
Relay
Contacts

De-energized
7 to 9 closed
8 to 9 open

Energized (non-
latching)
7 to 9 open
8 to 9 closed


2.0 SPECIFICATIONS

2.1 ELECTRICAL

2.1.1 COMMON ELECTRICAL SPECIFICATIONS
FOR DYNZ-60010, DYNZ-60012 AND DYNZ-60013
Ambient Operating Temperature:
-40 to +18

5

°F (-

40 to +8

5

°C).

Maximum Operating Current: 0.20 amperes.
Input Signal Voltage: 0 7 Vrms minimum into 33 k
ohm load.
Trip Setpoint: Adjustable 325 to 10,000 Hz.
SW1: Factory set at 1100 Hz.
SW2: Factory set at 3600 Hz.
Repeatability: ±5 Hz or ±1%, whichever is greater.

2.1.2 ELECTRICAL SPECIFICATIONS FOR DYNZ-
60010
Power Input:
8 to 40 Vdc.
Voltage Transients: Withstand 200 volts forward and
reverse peaks of 10 milliseconds duration at 5 ohms
source input impedance. Withstand 80 volts forward
and reverse peaks of 50 milliseconds duration at 50
ohms source input impedance.
Hysteresis:
SW1: Crank dropout, non-latching; nominal 165 Hz
SW2: Overspeed, latching; 100% of setpoint.
Relay Contact Rating: 10 amperes at 30 Vdc
resistive.
Overspeed Response Time: With the overspeed set
at 4140 Hz and a steady input frequency of 3600 Hz,
then switching the input frequency to 5000 Hz must
result in the overspeed relay operating in 90
milliseconds or less.

2.1.3 ELECTRICAL SPECIFICATIONS FOR DYNZ-
60012
Power Input:
59 to 88 Vdc.
Voltage Transients: Withstand 200 volts forward and
reverse peaks of 10 milliseconds duration at 50 ohms
source input impedance. Withstand 80 volts forward
and reverse peaks of 50 milliseconds duration at 50
ohms source input impedance.
Hysteresis:
SW1: Crank dropout, non-latching; nominal 165 Hz
SW2: Overspeed, non-latching; 0% of setpoint.
Relay Contact Rating: 0.75 amperes at 88 Vdc
resistive.
Overspeed Response Time: With the overspeed set
at 4140 Hz and a steady input frequency of 3600 Hz,
then switching the input frequency to 5000 Hz must
result in the overspeed relay operating in 75
milliseconds or less.

2.1.4 ELECTRICAL SPECIFICATIONS FOR DYNZ-
60013
Power Input:
8 to 40 Vdc.
Voltage Transients: Withstand 200 volts forward and
reverse peaks of 10 milliseconds duration at 50 ohms
source input impedance. Withstand 80 volts forward
and reverse peaks of 50 milliseconds duration at 50
ohms source input impedance.
Hysteresis:
SW1: Crank dropout, non-latching; nominal 165 Hz
SW2: Overspeed, non-latching; 0% of setpoint.

Note

Barber-Colman believes that all information provided
herein is correct and reliable and reserves the right to
update at any time. Barber0Colman does not assume
any responsibility for its use unless otherwise expressly
undertaken.

Caution

As a safety measure, Barber-Colman Company
recommends that all engines and turbines be equipped
with an independent overspeed shutdown devise.

Uncontrolled Document

For

H

istorical

Reference Only