beautypg.com

Dc output wiring sizing, Figure 2: individual ac feed wiring architecture, Rectifiers – Panduit DPOE PN380C User Manual

Page 9

background image

DP

O

E™ Power System User Manual

Part Number: PN380C

Rectifiers

1

2

3

Feed 1

Feed 2

AC In

N+1 DC Out

Feed 3

Figure 2: Individual AC Feed Wiring Architecture


Each individual AC feed should be protected using a circuit breaker as listed in

Table 4: Recommended

AC Circuit Breaker and Wire Sizes.

Table 4: Recommended AC Circuit Breaker and Wire Sizes

Type of

Feed

Number of

Rectifiers

on an AC

Feed

Part Number

Maximum

Input

Voltage

Maximum

Rated AC

Current

(A)

Circuit

Breaker

Minimum

value (A)

90° C

Minimum

Wire

Gauge

(AWG) to

use at 30°

C ambient

Individual

AC

Feed

1

DPOEPWRR500 90

7

15

14

DPOEPWRR500 180

3.5

15

14

DPOEPWRR1250

90 17.6 20 12

DPOEPWRR1250

180 8.8 15 14

DC Output Wiring Sizing

There are two main considerations for sizing DC wire, ampacity and voltage drop. Ampacity refers to the
safe current-carrying level as specified by U.S.-based organizations such as Underwriters Laboratories
and the National Fire Prevention Association, which publishes the National Electric Code (NEC). Voltage
drop is simply the amount of voltage loss in a length of wire due to ohmic resistance of the conductor. DC
wire may be sized for either ampacity or voltage drop depending on branch load loop length and
conductor heating. In general, ampacity considerations will drive wire selection for short loop lengths (less
than 50 feet) and voltage drop will drive wire selection for long loop lengths (greater than 50 feet). The
National Electric Code table 310.16 provides ampacity values for various sizes, bundles, and insulation
temperature rated wire.

4