Outputs, Shows – Panduit DPOE PN380C User Manual
Page 11

DP
O
E™ Power System User Manual
Part Number: PN380C
Butt splices connectors
Power connector 
housing with wire leads 
48VDC 
Supply 
Power Connector on rear side of 
DP
O
E™ Power Patch Panel or
Compact 8 Midspan
Connector 
pinouts 
Figure 4: Connecting to a DPoE™ Power Patch Panel or Compact 8 Midspan
NOTE:
The included power harness has two wires for the A-feed power only (pins 1 & 2). 
The DP
O
E™ Power Patch Panel or Compact 8 Midspan supports an optional
redundant B-feed power option, but the terminals and wire leads are not attached to 
the power harness. 
 
Contact PANDUIT Technical Support for more information about connecting the 
redundant B-Feed power. (PANDUIT part # DPOEPWRDUAL should be used for 
redundant powering options) 
WARNING:
The power supply connections on the DP
O
E™ Power Patch Panel and the
Compact 8 Midspan are polarized. They will not function if power is wired 
improperly. 
Table 5: Minimum Recommended DC AWG for 90°C Cabling for Unprotected
Outputs
Total Rectifier Current Rating (A)
Wire and Lug Gauge
(AWG) using 90
°
C wire
(NEC Table 310.16)
10 16 
20 14 
25 12 
 
 
 
1
Table 310.16 uses Table 3B – Sizes of Conductors from BS EN 60950:2000, “Safety of Information
Technology Equipment,” December 2000 for non-building wiring.
6