Burner setup & boiler operation – PB Heat WV Series User Manual
Page 17

15
BURNER SETUP & BOILER OPERATION
BECKETT BURNER SPECIFICATIONS
Boiler
Model No.
Burner
Model No.
Burner
Head
Static
Plate
Nozzle Size
Pump
Pressure
Start-up Settings
Head
Setting
Air Shutter
Air Band
WBV-03-085
AFG-F3¹
F3
3-3/8"
0.75 80° B HAGO³
140 PSI
6.0
1
N/A
WBV-03-105
AFG-F4
F4
3-3/8"
0.90 80° B HAGO
140 PSI
6.0
0
N/A
WBV-04-095
AFG-F4
F4
3-3/8"
0.85 80° B DEL
4
140 PSI
6.0
0
N/A
WBV-04-125
AFG-F4
F4
3-3/8"
1.10 80° B HAGO³
140 PSI
5.0
2
N/A
WBV-04-150
AFG-F6
F6
2-3/4"
1.25 80° B HAGO
140 PSI
8.0
1
N/A
WV-05-175
AFG-MV1
V-1
-
1.50 60° B HAGO³
140 PSI
10.0
3
3
WV-05-195
AFG-MV1
V-1
-
1.65 60° B HAGO
140 PSI
10.0
9
3
CARLIN BURNER SPECIFICATIONS (WITH 98022 PSC MOTOR)
Boiler
Model No.
Burner
Model No.
Head Bar
Nozzle Size
Pump Pressure
Start-up Settings
Air Shutter
Air Band
WBV-03-085
EZ-1HP
0.60 - 0.65
0.65 70° A DEL³
150 PSI
Blank
0.60
WBV-03-105
EZ-1HP
0.85 - 1.00
0.85 70° A DEL
150 PSI
Blank
0.65
WBV-04-095
EZ-1HP
0.75
0.75 70° A DEL
4
150 PSI
Blank
0.60
WBV-04-125
EZ-1HP
0.85 - 1.00
1.00 70° A DEL³
150 PSI
Blank
0.85
WBV-04-150
EZ-1HP
1.10 - 1.25
1.25 60° B DEL
150 PSI
Blank
1.00
WV-05-175
99FRD
N/A
1.50 60° B HAGO³
150 PSI
Open
10% open
WV-05-195
99FRD
N/A
1.65 60° B HAGO
150 PSI
Open
45% open
RIELLO BURNER SPECIFICATIONS
Boiler
Model No.
Burner
Model No.
Burner Series
Nozzle Size²
Pump Pressure
Start-Up Settings
Turbulator
Air Damper
WBV-03-060
F3
Series 40
0.50 90° B
145 PSI
0.0
2.9
WBV-03-085
F5
Series 40
0.65 60° W³
170 PSI
1.0
2.45
WBV-03-105
F5
Series 40
0.85 60° W
165 PSI
2.5
2.8
WBV-04-095
F5
Series 40
0.75 80° B
4
160 PSI
0.5
2.25
WBV-04-125
F5
Series 40
1.00 60° W³
155 PSI
2.5
3.4
WBV-04-140
F5
Series 40
1.10 60° W
160 PSI
4.0
4.2
WV-05-175
F10
Series 40
1.35 60° B³
165 PSI
2.0
2.5
WV-05-195
F10
Series 40
1.50 60° B
170 PSI
2.5
2.8
Factory Installed Nozzles (Packaged Boilers or Burner Cartons) are indicated in Boldface.
1 Requires Low Firing Rate Baffle
2 Delavan Recommended
3 Shipped Loose with Packaged Boiler or Burner Carton
4 Not included with Packaged Boiler or Burner Carton
Table 5.1:
Beckett Burner Specifications
Table 5.2:
Carlin Burner Specifications (with 98022 PSC motor)
Table 5.3:
Riello Burner Specifications
BECKETT NX BURNER SPECIFICATIONS
Boiler Model No.
Burner Model
Nozzle Size
Pump Pressure
Start Up Head/Air
WBV-03-085
NX70LB
0.65 x 60° W DEL³
170
1.5
WBV-03-105
NX70LB
0.85 x 60° B HAGO
170
2.5
WBV-04-095
NX70LB
0.75 x 60° W DEL
4
170
2.0
WBV-04-125
NX70LD
1.10 x 60° W DEL³
140
1.0
WBV-04-150
NX70LD
1.25 x 60° W DEL
140
2.0
Note: Burner used to fire the WBV-03-.085 and 1.05 rate is also required to fire the WBV-04-.95 rate with nozzle indicated in above chart.