Troubleshooting – Lochinvar SMART SYSTEM 502 - 2072 User Manual

Page 32

background image

3

Troubleshooting

32

FAULT

CAUSE

CORRECTIVE ACTION

No Display

- No 120 VAC supplied to unit.

• Check external line switch, fuse, or breaker.

• Check position of ON/OFF switch. Turn switch to the
ON position.

• Check 120 VAC through the ON/OFF switch. No
voltage through switch, replace switch.

- Bad wiring connection.

• Check wiring harness connection between the display
board and the main control board. Connect the harness
at both points.

- Blown fuse.

• Replace fuse F6 on the main control board, see

FIG. 3-1 on page 31 of this manual.

- Bad display board.

• Replace board.

- Bad main control board.

• Replace main control board.

No Burner

Operation

- Main control board temperature set point
satisfied.

• Review temperature setting.

- Remote thermostat satisfied.

• Review remote thermostat setting.

-

Outside air temperature above Warm

Weather Shutdown (WWSD) set point for
main control board.

• Check location of outside air sensor. Check
resistance of outdoor air sensor and compare to Table
3D on page 33 of this manual.

- Unit locked out on fault.

• Consult display for specific fault. Refer to fault
descriptions on pages 35 - 42 of this manual for
corrective

actions.

Unit Does Not

Modulate to

100%

- Ramp delay active.

• Check ramp delay parameter settings. Optional PC
software required.

• Turn ramp delay feature off. See page 18 of this
manual for instructions on how to turn this feature off.

- Boiler controlled by BMS.

• Check BMS parameter settings. Optional PC
software

required.

- Outlet temperature too high.

- Delta T too high.

Table 3A Troubleshooting Chart - No Display

Copper-fin II/IIE Boiler, Water Heater and Pool

Service Manual